FIGURE 3.2.a.1 Diagram of input/output bus bars and terminal blocks (100kVA, 150kVA, 225kVA UPS, Input voltage 480Vac)
Location of bus bars and terminal blocks
100kVA : 43.3" (1100mm)
150kVA : 47.2" (1200mm)
225kVA : 55.1" (1400mm)
UPS module
Battery
Input
BN,BP
AC
Input
A,B,C
Bypass
Input
A40,B40,C40
G8000MM Installation and
Operation
H=79.7" (2025mm)
D=29.9" (760mm)
N40,N50
External
wiring block
AC
Output
A50,B50,C50
Manual
Detailed Terminals
For power terminals, use 5/16" (8mm) Diameter bolts.
UPS module
AC Input
Bypass Input
A
B
C
A40 B40 C40
DC Input
BN BP
N40
N50
AC Output
A50 B50 C50
39