Toshiba G8000MM Series Installation And Operation Manual page 29

Hide thumbs Also See for G8000MM Series:
Table of Contents

Advertisement

Voltage THD
Transient Response
Transient Recovery
Overload Capacity
Output Current Limit
Crest Factor
Withstand Rating
Reliability
Cooling
Operating
Temperature
Relative Humidity
Heat Rejection
18,353
(kBTU/h)
Efficiency (AC-AC)
93.7%
Audible Noise
68 dB
@ 1m
Altitude
Location
Enclosure
Paint Color
Standards
UL1778; CUL22.2, No. 107.1; ANSI C62.41 (IEEE 587 Cat B); NFPA 70, OSHA,
Typical UPS AC-AC Efficiencies at Various Loads
UPS
25% Load
100 kVA
90.6%
150 kVA
91.2%
225 kVA
90.0%
300 kVA
89.2%
375 kVA
89.2%
500 kVA
91.0%
625 kVA
91.5%
750 kVA
91.5%
G8000MM Installation and Operation Manual
2% maximum THD at 100% Linear Load
5% maximum THD at 100% Non-Linear Load
+/-2% maximum at 100% load step
+/-1% maximum at Loss/Return of AC power
+/-5% maximum at Load Transfer to/from Static Bypass
Less than 16.7 ms
125% for 10 minutes; 150% for 1 minute
150% Full Load Current
65kA (with optional fuse)
3,000,000 Hr. with Bypass/ 140,000 without Bypass
ENVIRONMENTAL
32゚F to 104゚F ( 0゚C to 40゚C).
Recommended : 68゚F to 86゚F ( 20゚C to 30゚C)
5% – 95% Non Condensing
28,465
44,105
60,894
93.5%
93.3%
93.8%
72 dB
76 dB
@ 1m
@ 1m
0 to 9000 feet (No Derating)
Indoor (free from corrosive gases and dust)
Munsell 2.8Y7.7/0.3 (Mist White)
50% Load
75% Load
93.5%
93.8%
93.3%
93.8%
92.7%
93.4%
92.9%
93.6%
92.9%
93.5%
93.7%
94.3%
93.5%
93.8%
93.5%
93.8%
2.3
Forced Air
76,117
96,271
93.8%
94.1%
78 dB @ 1m
NEMA 1
ISO9001,
100% Load
93.7%
93.5%
93.3%
93.8%
93.8%
94.1%
94.1%
94.1%
120,339
144,407
94.1%
94.1%
80 dB @ 1m
19