Checking And Adjusting; Gas Valve Safety Shutdown Test; Pilot Burner Adjustment; Main Burner(S) Inspection - ECR International PENNCO FSB 3 Series Installation, Operation & Maintenance Manual

Gas-fired hot water induced draft boilers
Hide thumbs Also See for PENNCO FSB 3 Series:
Table of Contents

Advertisement

15.1 Gas Valve Safety Shutdown Test

!
WARNING
Electrical shock hazard. Follow instructions to turn
off electric power. Failure to do so could result in
death or serious injury.
Ignition system safety shutoff device must be tested after
placing boiler in operation.
With main burners firing, disconnect ignition cable from
intermittent pilot control box. Gas valve should shut off
main burners. TURN OFF ELECTRIC POWER to boiler before
reconnecting ignition cable, to prevent electric shock.
15�2 Pilot Burner Adjustment
1.
Remove screw cover over pilot adjusting screw.
2.
Insert small screwdriver and adjust flame as needed
See Figure 14 & 15. Turn screw counterclockwise
to increase flame, clockwise
Replace screw cover over pilot adjusting screw.
15�3 Main Burner(s) Inspection
Main burners do not require primary air adjustment and are
not equipped with primary air shutters.
Main burner flames form sharp blue inner cones in softer
blue outer mantel, with no yellow. Puffs of air from blowing
on flame or stamping on floor will cause flames to turn
orange momentarily. This is not unusual. Remain still when
observing main burner flames. See Figure 16.
If flame appearance is not correct, check main burner
orifices, burner throat and flame ports for dust and lint
obstruction. It may be necessary to remove rollout shield
to observe main burner flames. Replace rollout shield after
observation.
15�4 Adjusting Limit Controls
Instructions for each control are included with the controls.
See Appendix A.3.
Recommended Boiler Water Temperatures
Settings can be changed after you have had some idea how
the system works. Example: If your system does not give
quite enough heat in very cold weather, you can raise limit
setting to 190°F.
Instruction for final adjustment of thermostat are packaged
with thermostat.

15 - CHECKING AND ADJUSTING

Figure 14
to decrease.
Figure 15 - Pilot Flame Adjustment
3/8" to
1/2"
Flame
Figure 16
Main burner flame should form sharp blue inner mantel
with no yellow.
29
- Automatic Gas Valve
Ignition Electrode
- Main Burner Adjustment
PN 240013101 Rev. A [08/15/2020]