ECR International PENNCO FSB 3 Series Installation, Operation & Maintenance Manual page 18

Gas-fired hot water induced draft boilers
Hide thumbs Also See for PENNCO FSB 3 Series:
Table of Contents

Advertisement

Figure 9 - Horizontal Venting Clearances
D. Vent Termination
о Venting system shall terminate at least 3 feet
(0.9 m) above any forced air inlet located within
10 feet (3 m).
о Venting system shall terminate at least 4 feet
(1.2 m) below, 4 feet (1.2 m) horizontally from,
or 1 foot (300 mm) above any door, window, or
gravity air inlet into any building.
о Bottom of vent shall be located at least 12
inches (300 mm) above grade.
о Termination of vent shall be not less than 7 feet
(2.13 m) above adjacent public walkway.
о Vent terminal shall not be installed closer than
3 feet (0.9 m) from inside corner of L shaped
structure.
о Termination of vent should be kept at least 3
feet (0.9 m) away from vegetation.
о Venting system shall not terminate underneath
any deck, patio, or similar structure.
8 - HORIZONTAL VENTING INSTRUCTIONS
о United States - Terminate vent system at least
4 feet (1.22 m) horizontally from, and in no
case above or below, unless a 4 feet (1.22m)
horizontal distance is maintained, from electric
meters, gas meters, regulators and relief
equipment. See Figure 9.
о Canada - Terminate vent system at least 6
feet (1.83 m) horizontally from, and in no case
above or below,unless 6 feet (1.83 m) horizontal
distance is maintained, from gas and electric
meters, regulators and relief equipment.
о Venting system shall terminate at least 4 feet
below any eave, soffit, or roof overhang.
о Place vent on wall away from prevailing winter
wind. Locate or guard vent to prevent accidental
contact with people or pets.
о Terminate vent above normal snow-line. Avoid
locations where snow may drift and block vent.
Ice or snow may cause boiler to shut down if
vent becomes obstructed.
о Under certain conditions, flue gas will condense,
forming moisture. Take steps to prevent building
materials at vent terminal from being damaged
by exhaust of flue gas.
18
PN 240013101 Rev. A [08/15/2020]