Startup/Troubleshooting Form - Johnson Controls RL Series Installation Operation & Maintenance

Water source heat pumps, 7–25 tons
Hide thumbs Also See for RL Series:
Table of Contents

Advertisement

DEALER:
PHONE #:
PROBLEM:
MODEL #:
SERIAL #:
COOLING CYCLE ANALYSIS
AIR
°F
°F
COIL
COAX
LOAD
°F
PSI
BRINE IN
Water to Water Application
Heat of Extraction/Rejection = GPM x 500 (485 for water/antifreeze) x ∆T
Note: DO NOT hook up pressure gauges unless there appears to be a performance problem.
HEATING CYCLE ANALYSIS
AIR
°F
°F
COIL
COAX
LOAD
°F
PSI
BRINE IN
Water to Water Application
DATE:
Unit Amp Draw:
Line Voltage:
EXPANSION
VALVE
LIQUID LINE
°F
PSI
BRINE OUT
Unit Amp Draw:
Line Voltage:
EXPANSION
VALVE
°
F
LIQUID LINE
°F
PSI
BRINE OUT

Startup/Troubleshooting Form

Loop:
Open
Closed
COAX
SOURCE
°F
°F
°F
PSI
PSI
BRINE IN
BRINE OUT
Loop:
Open
Closed
COAX
SOURCE
°F
°F
PSI
PSI
BRINE IN
BRINE OUT
35
RL SERIES INSTALLATION MANUAL
PSI
=
SAT °F
°F
SUCTION
COMPRESSOR
REVERSING
VALVE
DISCHARGE
Hot Water
-
Generator
°
F
PSI =
Superheat
°F
°F
Subcooling
PSI
=
SAT °F
°F
SUCTION
COMPRESSOR
REVERSING
VALVE
DISCHARGE
Hot Water
-
Generator
°
F
PSI =
Superheat
°F
°F
Subcooling
°
SAT F
°
SAT F