8 Refrigerant and water piping
Refrigerant circuit

Minimum area requirements
In case of total refrigerant amount ≥1.84 kg, the unit should be installed, operated and stored in a room with a floor area
larger than the minimum criteria. Use following graphic and table to determine these minimum criteria:
Refrigerant
Minimum Area
Amount (kg)
(m
) (H:2.2m)
2
1.84
28.81
1.9
30.72
2.0
34.09
2.1
37.53
2.2
41.19
2.3
45.02
2.4
49.02
2.5
53.19
2.6
57.53
2.7
62.04
2.8
66.72
2.9
71.58
?
N O T E
In case of not achieving the minimum floor area, contact with your dealer.

Refrigerant piping size
Piping connection size of outdoor unit & indoor unit
Piping
Model
length
Gas pipe
2HP
3~50m
Ø 12.7 (1/2")
2.5HP
3~50m
3~27m
Ø 15.88 (5/8") (*)
3HP
27~40m
Ø 15.88 (5/8")
?
N O T E
(*): The refrigerant gas and liquid piping size for 2/2.5/3HP are different between outdoor and indoor unit, so refrigerant pipe adapters are
required. These pipe adapters are factory supplied with the outdoor unit:
Model
2 HP
Ø15.88→Ø12.7
2.5 HP
Ø15.88→Ø12.7
3.0 HP
98
TCGB0123 rev.2 - 10/2019
100
90
80
70
60
50
40
30
20
10
0
1.8
Outdoor unit
Pipe Connection size
Liquid pipe
Ø 6.35 (1/4")
Ø 9.52 (3/8") (*)
Ø 9.52 (3/8")
Pipe adapter
Gas pipe
Liquid pipe
-
Ø9.52→Ø6.35
Ø9.52→Ø6.35 (x2)
-
1.9
2.0
2.1
2.2
2.3
Total refrigerant amount in the system (kg)
Refrigerant pipe
(Between Outdoor unit and
Indoor unit)
Gas pipe
Liquid pipe
Ø 12.7
Ø 6.35
Ø 15.88
Ø 6.35
Ø 15.88
Ø 9.52
2.4
2.5
2.6
2.7
2.8
Indoor Unit
Pipe Connection size
Gas pipe
Liquid pipe
Ø 6.35 (1/4")
Ø 15.88 (5/8") (*)
Ø 9.52 (3/8") (*)
Ø 15.88 (5/8")
Ø 9.52 (3/8") (*)
Ø 15.88 (5/8")
Ø 9.52 (3/8") (*)
2.9