2 General data

Capacity tables

2.1 Capacity tables

2.1.1 Nominal capacity-performance tables

2.1.1.1 Considerations

The heating capacity tables show the capacity and performance data in integrated values (with defrost correction
factor included).
The nominal heating and cooling capacities are based on the EN 14511 standard: Piping length: 7.5 meters; Piping
lift: 0 meters.
Keywords:
CAP: Nominal capacity (kW)
COP: Coefficient of performance
EER: Energy efficiency ratio
DB: Dry bulb; WB: Wet bulb (ºC)
OAT: Outdoor ambient temperature (ºC)
WIT: Water inlet temperature (ºC)
WOT: Water outlet temperature (ºC)

2.1.1.2 Capacity-performance data


YUTAKI S
HP
Outdoor unit model
Indoor unit model
OAT
WIT / WOT
(DB/WB)
CAP
(Min./Nom./Max.)
30 / 35 ºC
COP (Nom.)
7 / 6 ºC
CAP (Nom./Max.)
47 / 55 ºC
COP (Nom.)
CAP (Nom./Max.)
30 / 35 ºC
COP (Nom.)
-7 / -8 ºC
CAP (Nom./Max.)
47 / 55 ºC
COP (Nom.)
OAT
WIT / WOT
(DB/WB)
CAP (Nom/Max)
12 / 7 ºC
EER (Nom.)
35 / -- ºC
CAP (Nom/Max)
23 / 18 ºC
EER (Nom.)
17
TCGB0123 rev.2 - 10/2019
2.0 HP
RAS-2WHVRP
RWM-2.0NRE(-W)
-
Unit
kW
1.85 / 4.30 / 6.50
-
5.25
kW
4.30 / 6.00
-
3.00
kW
4.50 / 5.30
-
kW
4.00 / 4.20
-
2.00
-
Unit
kW
4.00 / 5.00
-
4.00
kW
5.50 / 6.40
-
5.40
2.5 HP
RAS-2.5WHVRP
RWM-2.5NRE(-W)
Heating operation
1.85 / 6.00 / 8.60
4.80
6.00 / 7.50
2.85
5.30 / 6.20
2.8
2.70
4.70 / 5.00
1.80
Cooling operation
(Using cooling kit accessory)
5.30 / 6.00
3.60
6.30 / 7.70
5.30
2
3.0 HP
RAS-3WHVRP
RWM-3.0NRE(-W)
2.1 / 8.00 / 11.0
4.60
8.00 / 9.50
2.80
5.80 / 7.50
2.70
5.00 / 5.50
1.75
6.50 / 7.00
3.35
7.00 / 9.00
5.00