Troubleshooting 17
IPM error
Detective actuators:
Outdoor unit main PCB
Compressor
Transistor PCB
Detective details:
When more than normal operating
current to IPM in main PCB flows,
the compressor stops.
After the compressor restarts.
If the same operation is repeated
within 40sec,
the compressor stops.
If
and
repeats 5 times,
the compressor stops permanently.
Forecast of cause:
1. Defective connection of electric
components
2. Outdoor Fan Operation failure
3. Outdoor heat-exchanger clogged
4. Compressor failure
5. Main PCB failure
6. Transistor PCB failure
Indicate or Display:
Indoor unit
Operation lamp: 6 times Flash,
Timer lamp
Wired remote
Error code : [E : 65]
Outdoor unit (AOUG36/48LMAS1)
Mode Error
2
: Light OFF
Test 1 : Check connections of outdoor unit electrical
components
Check if
the terminal connection
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or miss-wiring,
reset the power.
OK
Test 2 : Check outdoor fan, heat-exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
OK
Test 3 : Check outdoor fan
Check Outdoor Fan Motor. (Refer to Troubleshooting 26)
>> If the Fan Motor is failure, replace it.
OK
Test 4 : Check compressor
Check Compressor. (PARTS INFORMATION 2)
OK
Test 5 : Check transistor PCB
Check Transistor PCB
>>If Transistor PCB is abnormal, replace it.
OK
Test 6 : Replace main PCB
If Test 1 - 5 do not improve the symptom, change Main PCB.
03-24
: 5 times Flash
A
B
C
D
E
6
5
: Light ON
n : n times blinking
is loose.
F