 Heat pump prohibition control
Perform heating by external heater only. Indoor unit is continuous thermostat off.
Operation
Heater on
DIP-SW101-3
Indoor unit fan
setting for
external heater
Heater off
DIP-SW101-3
Indoor unit fan
setting for
external heater
• Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting "Thon".
Tr-Ts ≥ 0.9°F
(0.5°C)
• Operation status
Heating operation
Room temperature
Air conditioner
Heater
DIP-SW101-3 On
Fan
DIP-SW101-3 Off
NOTE: In following operations, compressor will be on.
• Other than heating
• Test run
4-4. Details of function
Heater is on as shown in following diagram of heating
temperature.
On
Heater is off as shown in following diagram of heating
temperature.
Other than heating mode
Error occurred
Enabled
Forced thermostat off
Fan stop protection
Off
Heater is off as shown in following diagram of heating
temperature.
Other than heating mode
Disabled
Error occurred
Forced thermostat off
Tr-Ts
Off
Tr-Ts (=Thon) ≤ -0.9°F (-0.5°C)
On
On
Off
0.9°F (0.5°C)
Set temp.
-0.9°F (-0.5°C)
On
Off
12 V
0 V
On
Off
On
Off
- (05-38) -
Condition
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
3 min or more
1 min
1 min