3. COMPRESSOR FREQUENCY LIMITED BY OUTDOOR TEMPERATURE
Frequency of compressor is limited
by outdoor temperature as shown below.
Minimum frequency in cooling or dry operation
AOU24RGLX
AOU30RGLX
AOUG36LMAS1
AOUG48LMAS1
under 14 ˚F
over 14 ˚F (-10 ˚C)
(-10 ˚C)
under 32 ˚F (0 ˚C)
40 rps
32 rps
40 rps
32 rps
under 26.6 ˚F
over 26.6 ˚F (-3 ˚C)
(-3 ˚C)
under 120.2 ˚ F (49 ˚C)
26 rps
20 rps
over 32 ˚F (0 ˚C)
over 50 ˚F (10 ˚C)
under 50 ˚F (10 ˚C)
under 100 ˚F (38 ˚C)
25 rps
25 rps
over 120.2 ˚F
(49 ˚C)
25 rps
04-04
over 100 ˚F
(38 ˚C)
12 rps
25 rps
16 rps
25 rps