Parts information 8
Discharge pressure sensor (AOUG36/48LMAS1)
Check Point : Check Voltage from Main PCB
With the connector connected to the PCB,
measure the voltage between CN92:2-3 of the Main PCB.
DC
+
-
Characteristics of pressure sensor
4.5
0.5
0
Pressure [MPa]
CN92
DISCHARGE
RED
1
1
PS
PRESSURE
WHITE
2
2
SENSOR
BLACK
3
3
5.0
03-56