CHAPTER 1 - PRE-INSTALLATION REQUIREMENTS
1.6.

Combustion Air Contamination

WARNING
If the EXALT combustion air inlet is located in an
area likely to cause or contain contamination, or if
products which could contaminate the air cannot
be removed, the combustion air must be repiped
and terminated at another location. Contaminated
combustion air will damage the unit and its burner
system, and can result in substantial property
damage, serious injury, or death.
DANGER
Do not operate the EXALT if the combustion
air inlet is located near a laundry room or
pool facility. These areas will always contain
hazardous contaminants.
Pool, laundry, common household, and hobby
products often contain fluorine or chlorine
compounds. When these chemicals pass
through the burner and vent system, they can
form strong acids. These acids will corrode the
heat exchanger, burner components, and vent
system, causing serious damage and possible
flue gas spillage or water leakage into the
surrounding area.
Please read the information listed on the
right. If contaminating chemicals are located
near the area of the combustion air inlet, the
installer must pipe the combustion air inlet to
an area free of these chemicals.
Failure to comply with these instructions
will result in substantial property damage,
serious injury, or death.
DANGER
If the combustion air is taken from the room,
an air grille must be installed to provide air for
combustion. The air grilles should be sized in
Description
3" Vent Adapter
3" Roof & Side Wall Straight Termination
3" Side Wall & 45° Elbow Termination
3" Side Wall Tee Termination
6
Table 2 - Approved AL29-4C® Stainless Steel Vent Adapters and Terminations
SelKirk / Heatfab
Saf-T Vent EZ Seal or
Saf-T Vent SC
Not required
accordance with ANSI Z223.1/ NFPA54 and/
or Natural Gas and Propane Installation Code
CAN/CSA B149.1.
The grilles providing air supply taken from
within the property should be clearly labeled
"AIR SUPPLY, DO NOT COVER OR RESTRICT.
FAILURE TO PROVIDE ADEQUATE AIR FOR
COMBUSTION COULD RESULT IN SERIOUS
INJURY, OR DEATH."
Potential contaminating products
Spray cans containing chloro/fluorocarbons
Permanent Wave Solutions
Chlorinated wax
Chlorine based swimming pool chemicals / cleaners
Calcium Chloride used for thawing ice
Sodium Chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid / muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and clean-
ing solvents found in household laundry rooms
Adhesives used to fasten building products and
other similar products
Areas likely to contain these products
Dry cleaning / laundry areas and establishments
Beauty salons
Metal fabrication shops
Swimming pools and health spas
Refrigeration Repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
DuraVent
FasNSeal or CVS
Not required
9392
300186
9311TERM
300130 & 300186
9390TEE
300311
Z-Flex U.S. Inc.
Z-Vent
Not required
2SVSTPF03
2SVSTEX0345
2SVSTTF03