This section is used to define the main parameters of BACnet MS/TP line. The means
of the fields are:
In the field "Baudrate" the data rate of the BACnet line is defined;
In the field "Parity" the parity of the line is defined;
In the field
"BACnet Device
defined;
In the field
"MAC
Address" the MAC of BACnet node (from 0 to 254) is
defined;
The field
"Max
Master" specifies the highest allowable address for master
nodes. The value shall be less than or equal to 127;
The field
"Max Info
Frames" specifies the maximum number of information
frames the node may send before it must pass the token;
In the field
"Device
Instance" the of the BACnet MS/TP side of the converter
is defined.
NTP (N
T
P
ETWORK
IME
ROTOCOL
This section is used to define the parameters of NTP protocol. The means of the
fields are:
In the field
"Server
URL" the URL or the IP Address of the NTP Server is
defined;
In the field
"Poll Time
synchronization is defined.
ADFweb.com Srl – IT31010 – Mareno – Treviso
MS/TP):
Name" the name to give to the BACnet node is
)
(seconds)" the polling time for the time
User Manual OPC UA Server / BACnet Master
Document code: MN67B31_ENG
Revision 1.000
Figure 3d: "Set Communication
window
Figure 3e: "Set Communication
Time Protocol" window
INFO:
www.adfweb.com
Page 19 of 30
BACnet Master"
NTP (Network
Phone +39.0438.30.91.31
Need help?