Gira eNet Operating Instructions Manual page 4

Radio control unit 1-10v, 1-gang mini
Hide thumbs Also See for eNet:
Table of Contents

Advertisement

eNet
Radio control unit 1-10V, 1-gang Mini
o
Switch on mains voltage.
i The 1-10 V ballasts can be switched by briefly pressing the Prog button.
Status-LED (3) lights up: switched on
Status-LED (3) off: switched off
o
Perform commissioning.
i In installation positions that are not easily accessible, turn the operating mode switch to
position PC after commissioning and performing a function test. Subsequent changes to
the device settings can thus be carried out with the aid of the eNet-Server without involving
excessive installation work.
o
Mount the cover.
5.2 Commissioning
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
During commissioning, cover the parts carrying voltage on radio transmitters
and actuators and in their surrounding area.
i The actuator can also be commissioned with eNet server as an alternative to the
commissioning described here.
Connecting to radio transmitters
Load is switched off.
o
Press the Prog button for longer than 4 seconds.
The status LED (4) flashes after 3 seconds. The actuator is in programming mode for
approx. 1 minute.
o
Switch radio transmitter to programming mode (see radio transmitter instructions).
o
Trigger telegram on the radio transmitter.
The status LED lights up for 5 seconds.
The actuator is connected to the radio transmitter. The actuator and radio transmitter exit
the programming mode automatically.
i If the status LED of the control unit flashes 3 times at 1-second intervals for
approx. 5 seconds, then the programming operation was not successful. All the memory
locations in the actuator or radio transmitter are occupied.
i All On and All Off buttons of a radio transmitter are connected to the actuator automatically
as soon as the first connection to the radio transmitter takes place. Scene buttons must be
connected separately.
Disconnecting connection to a radio transmitter
o
Carry out the same steps as when connecting (see Connecting to radio transmitter).
The status LED (3) flashes quickly for 5 seconds. The actuator is disconnected from the
radio transmitter. The actuator and radio transmitter exit the programming mode
automatically.
i If there several connections or scene buttons for a radio transmitter, all connections must
be disconnected individually.
i All On and All Off buttons of a radio transmitter are disconnected automatically as soon as
the last connection to the radio transmitter is disconnected. Manual disconnection is not
possible.
Resetting actuator to default setting
All connections to radio transmitters are disconnected and parameters are reset to default
setting.
i The connections in the radio transmitters are preserved and must be deleted separately.
Load is switched off.
32581002
10499448
13.03.2014
4/11

Advertisement

Table of Contents
loading

This manual is also suitable for:

5421 00

Table of Contents