Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)*
Operation
Proof Test for Devices with Splitter Function (1.2O)
Step No.
Input value (mA)
1
20.0
2
12.0
3
4.0
4
23.0
5
0
Table 5.2
Figure 5.3
Usage in Zone 0, 1, 2/Div. 1, 2 only for KFD2-STC5-Ex1.2O and KFD2-STC5-
Ex1.2O.H
24
Output value
Current source/current
sink (mA) for KFD2-
STC5-(Ex)1.2O(.H)
20.0 ± 0.4
12.0 ± 0.4
4.0 ± 0.4
23.0 ± 0.4
< 0.2
Signal calibration
4 mA ... 20 mA
1
2
3
Zone 0, 1, 2
Div. 1, 2
Proof test set-up for KFD2-STC5-(Ex)1.2O(.H)
Voltage source (V) for
KFD2-STV5-Ex1.2O-1
5.0 ± 0.1
3.0 ± 0.1
1.0 ± 0.1
5.75 ± 0.1
< 0.1
KFD2-STC5-Ex1.2O
7-
8+
9
250 Ω
10-
11+
12
250 Ω
14+
15-
Voltage source (V) for
KFD2-STV5-Ex1.2O-2
10.0 ± 0.2
6.0 ± 0.2
2.0 ± 0.2
11.5 ± 0.2
< 0.1
Multimeter
(mA)
Multimeter
(mA)
I
supply
24 V DC
Power
Zone 2
supply
Div. 2

Hide quick links: