For The Service Tech - R290 - Beverage-Air BM Series User Manual

Table of Contents

Advertisement

User Manual for BM Refrigerators

FOR THE SERVICE TECH - R290

Refrigeration service should only be attempted by a trained trade professional certified to work on R290 systems.
Here are some critical service items.
This list does not qualify anyone to service the unit. It is a
reminder and checklist for the service tech. Keep these in
mind for R290 service:
Wire nuts are NOT to be used when changing an
electrical part.
The switches in this product are sealed, only exact
replacements may be used.
The process tubes are to be used for service access.
Cut out (with tubing cutter) refrigeration components
that are to be replaced. Do NOT un-braze.
Because R290 can be vented into the air during
service, the venting MUST be in an area free from
flame or spark. It must be near an open window or
door.
A sign noting service of a system containing propane
must be attached to the unit during refrigeration
service.
A combustible gas leak detector must be used to
inform anyone in the area when propane is present in
the air.
Rev. 08/20
Other Information:
Evacuation: It is critical that a refrigeration system be
leak free and internally dry. A thorough evacuation with
a good vacuum pump with a micron gauge attached is the
only way to ensure that the system is dry and ready for a
charge of refrigerant.
Charging: The system is critically charged and the proper
type and amount MUST be weighed in.
Overcharge symptoms: Unit will cool properly but
the suction line temperature will be unusually cold.
Compressor run time will be longer than normal.
Undercharge symptoms: Long run time, poor cooling and
a hot compressor dome are the main symptoms of an
undercharge.
Beverage-Air
Beverage-Air
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bm23hcBm23hc-b-28

Table of Contents