Thermocouple temperature input

T.C.
+
-
Type:
J-K-R-S-T-E-B-L-N
+VI24
GNDI
For the connection use a compensated cable. If using a screened cable, connect the screening to the earth bar as close as
possible to the probe. The screening is connected to earth on the hot joint of the probe.

Thermo resistance temperature input PT100 and PT1000 with 2 wires

PT100
PT1000
2 wires
+VI24
GNDI
Use a screened bipolar cable and connect the screening to the earth bar as close as possible to the module.
Attention: do not forget to bridge the VP1 port with + AI1 and the GNDI port with -AI1.
80990B_MHW_CAN-IO_12-2016_ENG
SHIELD
+AI1
- AI1
VP1
+AI1
-AI1
GNDI