ANALOGUE INPUT
IN VOLTAGE ±10 V
ANALOGUE INPUT
IN CURRENT
0/4 ... 20 mA
POTENTIOMETER
ANALOGUE INPUT
10
Max number
Type
Input filter
Input impedance
Sampling time
(for all channels)
Output format
Max error @ 25 °C
Protections
Electric insulation
Max number
Type
Input filter
Input impedance
Sampling time
(for all channels)
Output format
Max error @ 25 °C
Protections
Electric insulation
Max number
Type
Transducer power
Input filter
Input impedance
Sampling time
(for all channels)
Output format
Max error @ 25 °C
Protections
Electric insulation
8 (orderable in groups: 2, 4, 6, 8)
Single-ended voltage ±10 V
Low-pass, 3rd order
Cutting frequency: 20 Hz
> 1 MΩ
5 ms
Type: INT
Resolution: 13 bit (-4096 ... 4095)
LSB: 2,44 mV
±0,5% scale bottom
Polarity inversion: yes
Overvoltage: max 1 kV per 1 ms
Channel-channel: no
Channel-bus: 2 kV
8 (orderable in groups: 2, 4, 6, 8)
Current 0 ... 20 mA
Low-pass, 3rd order
Cutting frequency: 20 Hz
100 Ω
5 ms
Type: UINT
Resolution: 14 bit (0 ... 20 mA: 0 ... 16384
4 ... 20 mA: 3277 ... 16384)
LSB: 4,88 μA
±0,5% fondo scala
Polarity inversion: yes
Overvoltage: max 1 kV per 1 ms
Channel-channel: no
Channel-bus: 2 kV
8 (orderable in groups: 2, 4, 6, 8)
Potentiometer 2 kΩ min.
5 V, 150 mA max
Low-pass, 3rd order
Cutting frequency: 20 Hz
> 1 MΩ
5 ms
Type: UINT
Resolution: 12 bit
LSB: 1,22 mV
±0,5% scale bottom
Polarity inversion: yes
Overvoltage: max 1 kV per 1 ms
Channel-channel: no
Channel-bus: 2 kV
80990B_MHW_CAN-IO_12-2016_ENG