Messages and diagnostics
7.2 Function Codes
Response telegram
Modbus TCP:
Address Field
7 bytes
-
Modbus RTU:
Slave address
1 byte
-
Example
Reading in the rms phase currents:
● Address Field or slave address: The address of the 3RW5 soft starter is not entered in
the example (-).
● The CRC CHECK is not entered in the example (-).
● The phase currents start at register address 0x880F and include 6 registers.
● As feedback, the measured values of the current rms phase currents (I L1, I L2, I L3) are
returned with 100 A (0x0000 0x2710) each.
You can find the data table for the measured values in chapter Measured values (Page 158).
102
Function Code
1 byte
0x03
Function Code
Number of bytes
1 byte
1 byte
0x03
0x0C
Number of bytes
1 byte
0x0C
Register value
n registers
0x0000 0x2710
0x0000 0x2710
0x0000 0x2710
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
Register value
n registers
0x0000 0x2710 0x0000
0x2710 0x0000 0x2710
CRC
2 bytes
-