Level 0
Level 1 (On screen)
Speed Monitoring
(SPEED MONITOR)
Battery Monitoring
(BATTERY
MONITOR)
Level 2 (On screen)
Sensor
(DISCONN ON LOP SENS)
* Pressure Sensor Monitoring
Threshold
(DISCONN LOP THRESH)
* Monitor Pressure Switch Before
Crank
(MON LLOP BEFR CRANK)
* Monitor Pressure Sensor Before
Crank
(MON LOP BEFR CRANK)
* Disconnect On Oil Pressure
Switch
(DISCONN ON LLOP SW)
* Pressure Switch Transient Time
(LLOP SW TRANS TIME)
* Crank Disconnect At Alt
Frequency
(DISCONN AT ALT FREQ)
* Crank Disconnect At Engine
Speed
(DISCONN AT ENG SPEED)
* Engine Speed Sense Source
(SPEED SENSE SOURCE)
* Flywheel Teeth
(FLYWHEEL TEETH)
* Under-speed Shutdown
(UNDER SPEED SHUTDOWN)
* Under-speed Threshold
(UNDER SPD THRESHOLD)
* Under-speed Delay
(UNDER SPD DELAY)
* Over-speed Threshold
(OVER SPD THRESHOLD)
* Over-speed Delay
(OVER SPEED DELAY)
* Gross Over-speed Threshold
(GROSS OS THRESHOLD)
* Low Battery Voltage Action
(LOW VOLT ACTION)
* Low Battery Voltage Threshold
(LOW VOLT THRESHOLD)
* Low Battery Voltage Delay
(LOW VOLT DELAY)
* High Battery Voltage Action
(HIGH VOLT ACTION)
Parameters (On screen)
0.5 – 10.0 bar
Disable/Enable
Disable/Enable
Disable/Enable
0.0 – 3.0 sec
10 – 70 Hz
150 – 4000 rpm
Sensor input only/
Alternator output only/
Primary Sensor/Secondary
Alternator/
Primary Alternator/Secondary
Sensor
1 – 300
Disable/Enable
0 – 3600 rpm
1 – 60 sec
700 – 4500 rpm
0.1 – 20 sec
100 – 200 %
None/Notification/Warning/
Electrical Trip/Shutdown
8.0 – 31.0 volt
5 – 1800 sec
None/Notification/Warning/
Electrical Trip/Shutdown
Page | 12