Level 0
Level 1 (On screen)
(GENERAL TIMER)
Configuration
(ALT CONFIG)
Generator
(GENERATOR)
Voltage Monitoring
(VOLT MONITOR)
Level 2 (On screen)
(SAFETY MONITOR DELAY)
Mains Detect Delay
(MAINS DETECT DELAY)
* Alternator Detect Delay
(ALT DETECT DELAY)
(WARM UP DELAY)
Return To Mains Delay
(RETN-TO-MAINS DELAY)
* Engine Cooling Time
(ENG COOL TIME)
* Stop Action Time
(STOP ACTION TIME)
* Additional Stopping Time
(ADDN STOPPING TIME)
Load Transfer Delay
(LOAD TRANSFER DELAY)
Power Save Mode Delay
(PWR SAVE MODE DELAY)
Sounder Alarm Time
(SOUNDER ALARM TIMER)
Auto Exit Config Mode
(AUTO EXIT CNFG TMR)
* Alternator Present
* Number Of Poles
(NUMBER OF POLES)
(ALT AC SYSTEM)
* Min Healthy Voltage
(MIN HEALTHY VOLT)
Alternator
* Min Healthy Frequency
(MIN HEALTHY FREQ)
* Phase Reversal Detection
(PHASE REVERSE DETECT)
* Phase Reversal Action
(PHASE REVERSE ACTION)
* Auto Load Transfer
(AUTO LOAD TRANSFER)
* Genset Nominal Voltage
(NOMINAL VOLTAGE (L-L))
* Genset Nominal Frequency
(NOMINAL FREQUENCY)
* Under-voltage Shutdown
(UNDER VOLT SHUTDOWN)
* Under-voltage Shutdown
(UV SHUTDWN THRESHLD)
Warm-Up Delay
(ALT PRESENT)
* AC system
Threshold
Parameters (On screen)
1 – 300 sec
1 – 60 sec
0 – 60 sec
0 – 600 sec
0 – 300 sec
10 – 120 sec
0 – 120 sec
0 – 60 sec
5 – 1800 sec
1 – 300 sec
10 – 1800 sec
No/Yes
2/4/6/8
Single Phase 2 Wire/ Single
Phase 3 Wire/ Three Phase 4
Wire (1Ph 2 wire/1Ph 3
wire/3Ph 4 wire)
50 – 350 Volt Ph-N
10 – 75 Hz
Disable/Enable
None/Notification/Warning/
Electrical Trip/Shutdown
Disable/Enable
100 – 650 Volt L-L
10.0 – 75.0 Hz
Disable/Enable
50 – 295 Volt Ph-N
Page | 9