Control box for smoke function with damper exercising (10 pages)
Summary of Contents for Swegon CRM
Page 1
Controllable measurement unit, Ductwork Leakage Class 0 or 4 Quick Facts ► Type-approved method of measurement ► Ductwork leakage class 0 and 4 ► One commissioning constant (K factor) per size ► Manual control (standard) ► With provision for motorised control ►...
Circular airflow measurement and commissioning damper. setting angle For particulars of motorised control, we The CRM consists of a duct section with a damper and refer to the actuator supplier’s instructions. K-factors are measuring device. The connections are fitted with rubber shown on the product’s identification label.
(L dB), as a function of airfl ow and pres- wtot sure drop across the damper. By correcting with the correction factors from the table for CRM 1, Wtot the sound power level for each octave band (L wtot )can be obtained.
Page 4
CRM 1-160 CRM 1-200 70 dB 70 dB Wtot Wtot 500 m 1000 m CRM 1-250 CRM 1-315 70 dB 70 dB Wtot Wtot 400 l/s 500 500 l/s 1000 1000 2000 CRM 1-400 CRM 1-500 70 dB 70 dB...
Page 5
Sizing diagram, CRM 5, Class 4 Velocity – Pressure drop – Sound level • The diagrams should not be used for commissioning. • The diagrams show pressure and fl ow lines at various damper settings. • ∇ = Min. airfl ow required for obtaining suffi cient com- missioning pressure.