Installation Instructions for the
TBIQ-2-1-aa IQnomic Plus Module
GOLD/COMPACT
1. General
The IQnomic Plus is used for extra functions for which
inputs and outputs are not included as standard in the
control unit of the air handling unit.
2. Installation
Mount the IQnomic Plus at a suitable location. One helpful
hint is to mount the module at an unoccupied spot on the
rail inside the control cubicle of the air handling unit.
Wire the IQnomic to the control unit inside the electrical
equipment cubicle of the air handling unit.
Connect the communication cable, supplied with the unit,
to one of the connections on the module. It is not im-
portant which connection is used. The reason why there
are two connections is to make it possible to connect seve-
ral IQnomic in series.
Connect the other end of the communication cable to one
of the connections of the control unit, marked Internal
EIA-485.
Function selector switch
0 ReCO
(Intermittent night-time heating + extra control
2
sequence)* or Input/Output connections***
1 Coil heat exchanger*
2 Plate heat exchanger*
3 External supervision
4 Humidification*
5 AQUA Link*
6 External Cooling Control
7 All Year Comfort
8 Swegon Factory*
9 Preheater**
A Xzone heating* (see separate instructions TBLZ-1-50)
B Xzone heating* (see separate instructions TBLZ-1-50)
C Spare
D Spare
E Enhanced heating sequence*
F Spare
* Not COMPACT/GOLD LP
** Not COMPACT Air/Heat
*** Do not apply to GOLD RX/PX/CX/SD
3. Data
Terminal contacts:
2 x RJ 12 6/6
Voltage supply
(Via modular contact):
24V DC
Relay contacts
5A/AC3
12A/AC1
Ambient temp.
Normal:
-20 °C — 40 °C, 10 — 95 % RH
Degree of protection:
IP 20 to EN 60529
CE approval:
EN 61000-6-2, EN 61000-6-3
We reserve the right to alter specifications.
Figure 1
13
14
15
Function
selector
switch
1
2
3
Terminal number
1
Relay 1
2
4
Relay 2
5
7 →
Digital, IN 1
8 –
9 →
Digital, IN 2
10 –
11 +
12 – *
13 – *
0–10 V, OUT 2
14 +
15 – *
0–10 V, OUT 1
16 +
17 – *
0–10 V, IN 2
18 +
19 – *
0–10 V, IN 1
20 +
21 –
Digital sensor 2
22 s
23 –
Digital sensor 1
24 s
* Measuring zero. Internally connected.
GB.TBIQ2480.190318
16 17
18
19
20
21
22 23
4
L1
L2
4 5
6
7
8
9
10 11
External power supply, 24 V DC
www.swegon.com
24
12
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the TBIQ-2-1-aa IQnomic Plus GOLD and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Swegon TBIQ-2-1-aa IQnomic Plus GOLD

  • Page 1 4 Humidification* Terminal number 5 AQUA Link* 6 External Cooling Control Relay 1 7 All Year Comfort 8 Swegon Factory* Relay 2 9 Preheater** 7 → A Xzone heating* (see separate instructions TBLZ-1-50) Digital, IN 1 B Xzone heating* (see separate instructions TBLZ-1-50) 8 –...
  • Page 2 VA,you should wire the leads to terminals 201 (G) and 202 (G0). Wiring terminals 201-202 can be loaded with a total of max. 48 VA. ** See the appropriate instructions for CO2 sensors from Swegon, ELQZ- 2-504 or ELQZ-2-504-2. *** If the outdoor air damper does not have spring return, it is not necessary to wire the 24 V (G) supply voltage across the control relay (20-21).
  • Page 3: Input/Output Connections

    – External Alarm 2: For connection of External Alarm 2. – External reset: For connection of the pushbutton for resetting a tripped alarm. – External fire alarm: A fire alarm will trip if the input is not closed. www.swegon.com We reserve the right to alter specifications.
  • Page 4: Plate Heat Exchanger

    Fig. 4 10 11 * Digital temperature sensors require correct polarity. Be careful Fig. 3 when you wire the conductors. Contactor C1, conn. A1 Contactor C1, conn. 13 Contactor C1, conn. 14 www.swegon.com We reserve the right to alter specifications.
  • Page 5 Indicates the present supply airflow, from 0 to the AHU fans’ max speed. 0 - 10 V Out 2 Indicates the present extract airflow, from 0 to the AHU fans’ max speed. www.swegon.com We reserve the right to alter specifications.
  • Page 6 Relay output DO 1 (use Terminals 1-2) for controlling the humidifier’s solenoid valve or circulation pump, on/off. 16 17 22 23 10 11 Supply voltage Solenoid valve or circulation pump, evaporative humidifier (not Swegon) www.swegon.com We reserve the right to alter specifications.
  • Page 7 22 23 Digital input (Wiring terminals 7-8) can be used for pump alarms. Select normally open, normally closed or contactor function in the AHU’s hand-held micro terminal. 10 11 Circulation pump Pump alarm www.swegon.com We reserve the right to alter specifications.
  • Page 8 TBLZ-1-59 equipment cubicle 10 11 4.10 Swegon Factory The IQnomic Plus module is used for the Swegon Factory function (function selector switch set to position 8, see Fi- gure 1) where type BOOSTER low-velocity supply air termi- nals with damper motor are used.
  • Page 9 Wiring terminals 201-202 can be loaded with a total of max. 48 VA. 10 11 ** Digital temperature sensors require correct polarity. Be careful when you wire the con- ductors Fig. 10 Control of the circulation pump www.swegon.com We reserve the right to alter specifications.
  • Page 10 202 (G0). Wiring terminals 201-202 can be sensors require cor- loaded with a total of max. 48 VA. rect polarity. Be careful 16 17 22 23 when you wire the conductors. 10 11 Fig. 11 www.swegon.com We reserve the right to alter specifications.
  • Page 11 ** Digital temperature sensors require correct polarity. Be careful when you wire the conductors. 10 11 Fig. 12 Control of the circulation pump If the Season Heating function is activated. Optional setting: normally-open or normally-closed contact. www.swegon.com We reserve the right to alter specifications.
  • Page 12 – Connect the white/blue or light blue conductor to Termi- nal 15. – Connect the orange conductor to Terminal 16. Adapter for wall mounting, 8-pin, TBLZ-1-55 Electric air heater Swegon Standard with 8-pin control cable 24 V AC* (G0) Applicable to size 100/120 GOLD...

This manual is also suitable for:

Tbiq-2-1-aa iqnomic plus compact