Instructions for the Installation of the type TBLZ-3-50
Zone Control Box (X zone)
GOLD
1. General
The zone control box consists of two IQlogic
and one transformer (230 VAC/24 VAC) mounted inside a
metallic enclosure.
Necessary wiring terminals are provided for connection
to external components. The metallic enclosure has cable
gland screw caps for cable entry.
See also the separate guide to the Xzone functions.
2. Range of Application
Sometimes more than one temperature zone is required in
a ventilation system. Different temperature needs in vari-
ous parts of a building may be due to the perimeter wall
of the building facing north or south, diverse operations
conducted inside or other reasons, for instance. The func-
tion is designed for one extra temperature zone, max.
3. Installation
Secure the zone control box to a wall, the air handling unit
or the like by means of four screws.

4. Technical Data

Supply voltage
CE-approved to
Enclosure class
Ambient temperature
at relative humidity
Relay contacts
Weight
Dimensions (Width x
Height x Depth)
Fuse protection
Transformer
We reserve the right to alter specifications.
modules
+
230 V AC or 400 V AC,
max. 10 A
EN 61000-6-2,
EN 61000-6-3
IP 65
-40 °C – +55 °C
10 – 95%
2 A/AC3, 5 A/AC1
8 kg
300 x 400 x 120 mm
2-pin connector, 0.25 A, C
characteristic
24 V AC/24 VA
GB.TBLZ350.170214
www.swegon.com
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the TBLZ-3-50 and is the answer not in the manual?

Questions and answers

Summary of Contents for Swegon TBLZ-3-50

  • Page 1: Technical Data

    GB.TBLZ350.170214 Instructions for the Installation of the type TBLZ-3-50 Zone Control Box (X zone) GOLD 1. General The zone control box consists of two IQlogic modules and one transformer (230 VAC/24 VAC) mounted inside a metallic enclosure. Necessary wiring terminals are provided for connection to external components.
  • Page 2 (TBLZ-1-30), if required, to Terminals 131 and 132. Connect room sensor, TBLZ-24-2 (1-4 sensors), if required, to the IQlogic module with RJ45 contact, see separate installation instructions. See Section 6. Electric connections appear on the next page. www.swegon.com We reserve the right to alter specifications.
  • Page 3: Electrical Connections

    Blue Resistor, 2.2 kΩ Orange Black Brown White Green 0-10 V DC output signal Yellow 0-10 V DC control signal Brown G0 24 V AC White or grey G 24 V AC www.swegon.com We reserve the right to alter specifications.
  • Page 4 GB.TBLZ350.170214 6.2 Electric air heater/air cooler, DX www.swegon.com We reserve the right to alter specifications.
  • Page 5 COM POWER COM POWER Heat/Cool Com 1 Com 2 Heat/Cool Com 1 Com 2 Cable for internal communication Terminals for connection of the TBLZ-1-26-aa modular cable to the GOLD control unit, COM 1-3. www.swegon.com We reserve the right to alter specifications.
  • Page 6 GB.TBLZ350.170214 www.swegon.com We reserve the right to alter specifications.