• Quick-Start guide
• PowerSure family user manual on CD (also at www.liebert.com)
• Warranty card
• MultiLink
software CD; MultiLink serial cable (M3LS9P9S), 10 ft. (3m)
• RJ-11 cord, 7 ft. (2.1 m); USB cable, 6 ft. (1.8m)
For more details, refer to the PowerSure user manual on CD.
Para una información más detallada, consulte el manual del usuario de la
familia PowerSure en el CD.
I
NSTALLATION
Read all safety, installation and operating instructions in the PowerSure family user manual on the included CD or
at
www.liebert.com
before operating the UPS. Adhere to all warnings on the unit and in the manual.
1. Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area
of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and conductive
contaminants. Maintain a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an ambi-
ent temperature range of 32°F to 104°F (0°C to 40°C).
2. Plug the PSP's power cord into an AC outlet. Check the Site Wiring Fault Indicator on the rear; if it is illuminated,
refer to the Troubleshooting section.
3. Plug any computers and monitors into the orange receptacles for battery backup and surge protection; other
office machines that do not exceed the capacity of the UPS may be plugged into either of the two (2) black
receptacles, which provide surge protection only.
4. Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors.
5. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indi-
cator will illuminate (green).
6. Turn on connected equipment.
C
ONTROLS AND
This button controls output power to the connected
load and has three functions:
• Turns the PowerSure PSP ON
• Turns the PowerSure PSP OFF
• Silences PowerSure PSP alarms
TURN THE UPS ON: Press and release the main ON/OFF
button to start the UPS. An audible alarm will sound briefly.
TURN THE UPS OFF: When the PSP is ON, hold the main
ON/OFF button down for more than 2 seconds to shut it down.
An audible alarm will sound briefly.
SILENCE AN ALARM: When a UPS alarm is active, press and
release the main ON/OFF button to silence the audible alarm
(Exceptions: low battery, overload and overtemperature). DO
NOT hold the button down for more than 2 seconds or the PSP
will shut down.
CHECK THE PSP'S CONDITION: Three status indicators on
the front of the UPS illuminate to specify the status of the UPS
(see Troubleshooting section for details).
Utility Indicator
Green: Normal operation
Fault Indicator
Green: Overload/
Overtemperature
Red:
UPS fault
SITE WIRING FAULT INDICATOR (RED)
The Site Wiring Fault Indi-
Rear of UPS
cator on the rear panel, as
shown, illuminates red
when the UPS detects a
line-neutral reversal or a
poor neutral-ground. (See
Troubleshooting Chart if
indicator is illuminated.)
TRANSFER VOLTAGE SELECTORS (DIP SWITCHES)
The two-position DIP switch control on the rear panel, shown
above, allows the operator to select the utility transfer voltage
at which the UPS will switch to battery power. The factory
default settings are 100VAC - 135VAC. DIP switch positions for
each voltage setting are:
DIP switch settings
Left
Right
↑ Up
↑ Up
↑ Up
↓ Down
↓ Down ↑ Up
↓ Down ↓ Down
CAUTION
!
Never change the voltage settings while the UPS
is ON and powering connected loads. Change
DIP switches only when the UPS is OFF.
CAUTION
!
To ensure protection of the connected
equipment, the DIP switch settings should match
the nominal utility input voltage. DIP switch
settings not matching the nominal utility could
potentially damage connected equipment.
PowerSure
Quick-Start Guide for 350-650VA; 120V
B
OX
I
C
NDICATORS
OMMUNICATIONS
The PowerSure PSP will communicate with your computer in either of two ways: over its DB-9 port through Lie-
bert's MultiLink
MultiLink supplies useful monitoring data, such as input voltage and battery level, and will perform an orderly shut-
down of the computer system. Microsoft Windows XP and 2000 operating system utilities supply UPS status infor-
mation and will perform an orderly computer shutdown. Check your computer's OS features to determine whether
it has power management capability.
For MultiLink Serial Communications
• Connect the provided MultiLink serial cable to the DB-9 ports on the rear of the UPS and on the rear of your
computer.
• Install the MultiLink software—the software, installation instructions and the user manual are on the CD included
in the PowerSure PSP package.
For USB Communications (with operating system power management)
• Connect the USB cable provided with the UPS to the USB ports on the PSP and your computer. The PSP will
work automatically with the built-in power management software on Windows XP and 2000 or later.
• All USB models are compatible with Microsoft Windows 2000, Windows XP and Macintosh
S
PECIFICATIONS
Model Number
Power Rating VA/W
DIMENSIONS: in. (mm)
Unit
Battery Indicator
Green: On battery
W x D x H
Amber: Battery
Shipping
warning
W x D x H
WEIGHT: lbs (kg)
Unit
Shipping
DIP Switches
INPUT AC PARAMETERS
Surge Protection
Site Wiring
Fault
Rated Input Voltage
Indicator
(Red)
Voltage Range Without
Battery Operation
Frequency Range
Input Power Cord
OUTPUT AC PARAMETERS
Output Receptacles
Voltage (Battery mode)
Setting
Output Current
100 - 135VAC (default)
Waveform (Battery mode)
100 - 145VAC
Frequency
90 - 135VAC
Overload Warning
(Normal & Battery modes)
90 - 145VAC
Overload Shutdown
BATTERY PARAMETERS
Type
QuantityxVoltagexRating
Transfer Time
Backup Time:
Full Load
Half Load
Recharge Time
* Power ON/OFF/
Alarm Silence
* Utility Indicator
(Green)
* Battery Indicator
(Green/Amber)
* Fault Indicator
(Red/Green)
For details, see:
* Controls and Indicators
** Installation
*** Communications
®
software or by USB through Microsoft
Windows
PSP350MT-120
PSP500MT-120
350VA/210W
500VA/300W
3.7 x 9.5 x 8
3.7 x 9.5 x 8
(95 x 240 x 205)
(95 x 240 x 205)
6.7 x 13.1 x 11.5
6.7 x 13.1 x 11.5
(171 x 332 x 293)
(171 x 332 x 293)
10.2 (4.6)
10.2 (4.6)
12.6 (5.7)
12.6 (5.7)
570J
120VAC
90VAC - 145VAC, DIP switch selectable
(see DIP switch settings)
46.5 - 63.5 Hz (±0.1 Hz)
6 ft. (1.8m) attached, w/ NEMA 5-15 P
(4) NEMA 5-15R (orange)
Battery backup + surge protection;
(2) NEMA 5-15R (black)
Surge protection
120VAC ±8%
2.9 A
4.2 A
Stepped Sinewave
50 Hz or 60 Hz; auto sensing
>100%
>110%
Valve-regulated, nonspillable, lead acid
(1)x12Vx7Ah
(1)x12Vx7Ah
4 - 6 ms typical
At 77°F (25°C), resistive loading, with fully charged batteries
9 minutes
4 minutes
24 minutes
17 minutes
6 hours to 90% of rated capacity,
after full discharge into resistive load
PSP
Site Wiring Fault *
*** USB port
Indicator (Red)
DIP switches **
*** DB-9 port
Data Line ***
** Orange output
Protection
receptacles
Connectors
(battery backup and
surge protection)
** Black output
receptacles
(surge protection only)
6-ft. (1.8m)
power cord
Battery cover plate
(bottom of UPS)
Plug computers, monitors & network hubs
into orange receptacles
Plug this type of equipment into
black receptacles ONLY
Scanners
Inkjet printers
Fax machines
®
operating system features.
®
OS 10.2 or later.
PSP650MT-120
ENVIRONMENTAL (ALL MODELS)
650VA/390W
Operating
+32°F to + 104°F
Temperature
(0°C to +40°C)
Storage
+5°F to +104°F
3.7 x 9.5 x 8
Temperature
(-15°C to +40°C)
(95 x 240 x 205)
Relative
0% to 95%,
6.7 x 13.1 x 11.5
Humidity
non-condensing
(171 x 332 x 293)
Up to 10,000 ft.
Operating
(3000m)
10.2 (4.6)
Elevation
at 86°F (30°C)
without derating
12.6 (5.7)
< 40 dBA, at 1
Audible Noise
meter
AGENCY (ALL MODELS)
UL 1778, c-UL
Safety
Listed
ANSI C62.41,
Category A, Level 3
(IEEE 587,
Surge
Category A);
EN61000-4-5,
Level 3, Criteria A
EN61000-4-2,
ESD
Level 3, Criteria A
EN61000-4-3,
Susceptibility
Level 3, Criteria A
5.4 A
Electrical Fast
EN61000-4-4,
Transient/Burst
Level 4, Criteria A
FCC Part 15,
Emissions
Subpart B, Class B
Conducted
EN61000-4-6,
Immunity
Level 3, Criteria A
Harmonics
EN61000-3-2
Flicker
EN61000-3-3
(1)x12Vx9Ah
Transportation
ISTA Procedure 1A
5 minutes
14 minutes

Advertisement

loading

Summary of Contents for Emerson Liebert PowerSure PSP Series

  • Page 1 DISCONTINUED ™ PRODUCT PowerSure Quick-Start Guide for 350-650VA; 120V ’ * Power ON/OFF/ Site Wiring Fault * Alarm Silence *** USB port Indicator (Red) • Quick-Start guide * Utility Indicator DIP switches ** *** DB-9 port (Green) • PowerSure family user manual on CD (also at www.liebert.com) Data Line *** ** Orange output * Battery Indicator...
  • Page 2 ROUBLESHOOTING ROUBLESHOOTING HART The information below indicates various symptoms a user may encounter in the event If the UPS fails to operate properly, turn off the unit and repeat the steps in the Installa- the PowerSure PSP experiences a problem. Use this information to determine whether tion section of this manual.

This manual is also suitable for:

Liebert psp350mt-120Liebert psp500mt-120Liebert psp650mt-120