Dimensions –
YCIV0590E/V and YCIV0600S/P
Notes:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,
reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air patters and possible diminished performance. Johnson Controls' unit controls will optimize the operation without nuisance
high pressure safety cutouts; however, the system designer MUST consider potential performance degradation.
Access to the unit control center stipulates the unit is no higher than on spring isolators. Recommended minimum clearances: side to wall
- 2m; rear to wall - 2m; control panel end to wall - 1.2m; top - no obstructions whatsoever; distance between adjacent units - 10'. No more
than one adjacent wall may be higher than the unit.
84
SI
38
POWER ENTRY
254 WIDE X 330 HIGH
102
VIEW B-B
POWER ENTRY IS ON BOTTOM OF PANEL
B
(EDGE OF UNIT
TO COOLER
CONNECTION)
YCIV
A
485
0590E/V
442
0600S/P
CONTROL ENTRY
76 WIDE X 343 HIGH
44
C
B
C
A
B
C
D
714
2146
2865
739
2286
2797
305
VIEW C-C
B
2238
VIEW A-A
JOHNSON CONTROLS