General Unit Data
Number of Independent Refrigerant Circuits
Refrigerant Charge, R-134a, Ckt.-1/Ckt.-2, lbs
Oil Charge, Ckt.-1/Ckt.-2, gal.
Glycol Charge (43% concentration), gal
Comp.s, Semihermetic Screw
Quantity per Chiller
Condensers, High Efficiency Fin/Tube with Integral Subcooler
Total Chiller Coil Face Area, ft2
Number of Rows
Fins per Inch
Condenser Fans
Number, Ckt.-1/Ckt.-2
Low Noise Fans
Fan Motor, HP/kWi
Total Chiller Airflow, cfm
Ultra Quiet Fans
Fan Motor, HP/kWi
Total Chiller Airflow, cfm
Dual Speed Fans - Normal Speed
Fan Motor, hp
Total Chiller, CFM
Dual Speed Fans - Lower Speed
Fan Motor, hp
Total Chiller, CFM
High Static Fans
Fan Motor, hp
Total Chiller, CFM
Evaporator, Direct Expansion
Water Volume, gals.
Maximum Water Side Pressure, PSIG
Maximum Refrigerant Side Pressure, PSIG
Minimum Chilled Water Flow Rate, gpm
Maximum Chilled Water Flow Rate, gpm
Water Connections, inches
Contact your nearest Johnson Controls Sales Office for weight data.
JOHNSON CONTROLS
MODEL NUMBER (YCIV____ S/P)
60Hz
0287
50Hz
1070
3
185/170/170
5/4/4
5.4
3
381
3
17
5/4/4
2/1.8
169000
2/1.50
169000
2
143000
2
109200
5
169000
202.0
150
235
250
1200
10
STANDARD EFFICIENCY
0307
0357
1180
1340
3
185/185/170
185/185/230
5/4/4
5/5/5
5.5
3
411
469
3
17
5/4/4
5/5/6
2/1.8
2/1.8
182000
208000
2/1.50
2/1.50
182000
208000
2
143000
165000
2
109200
126000
5
182000
208000
236.0
236.0
150
150
235
235
300
300
1200
1200
10
FORM 201.23-EG1 (1007)
0397
1500
3
3
230/230/230
5/5/5
6.0
6.3
3
3
528
3
3
17
17
6/6/6
2/1.8
234000
2/1.50
234000
2
2
165000
2
2
126000
5
5
234000
236.0
150
235
300
1200
10
10
57