Electrical Notes

1. As standard, all units have single point power connection. Contact factory for information regarding dual
point power units.
2. Maximum Inverse Time Circuit Breaker or Dual Element Fuse - 225% of the largest compressor RLA
plus the sum of all other loads per NEC 440.22 (A).
3. MCA - Minimum Circuit Ampacity - 125% of the largest compressor RLA plus 100% of the remaining
compressor RLA's plus the sum of all condenser fan FLA's per NEC 440.33
4. Recommended time delay or dual element fuse size - 150%of the largest compressor RLA plus 100%
of the remaining compressor RLA's plus the sum of all condenser fan FLA's.
5. RLA - Rated Load Amps - rated in accordance with UL standard 1995.
6. Local codes may take precedence.
7. Control KVA includes operational controls and evaporator heaters.
8. System inrush current is less than RLA due to the use of York Variable Speed Drive technology. Typical
Compressor Starting Current ( first four seconds of startup):
Rated Voltage
380-400/50/3
380/60/3
460/60/3
9. Voltage Utilization Range:
Rated Voltage
380-415/50/3
380/60/3
460/60/3
LEGEND
C.B.
CIRCUIT BREAKER
D.E.
DUAL ELEMENT FUSE
DISC SW
DISCONNECT SWITCH
FACT CB
FACTORY-MOUNTED CIRCUIT BREAKER
FLA
FULL LOAD AMPS
HZ
HERTZ
MAX
MAXIMUM
MCA
MINIMUM CIRCUIT AMPACITY
MIN
MINIMUM
MIN NF
MINIMUM NON-FUSED
RLA
RATED LOAD AMPS
S.P. WIRE
SINGLE-POINT WIRING
NOTES:
1. U.L. Label is provided on 50 and 60 Hz units for these electrical wiring configurations.
2. –– –– –– –– –– –– Dashed Line = Field Provided Wiring.
3. The above recommendations are based on the National Electric Code and using copper conductors only. Field wiring must also comply
with local codes. Group Rated breaker must be HACR type for cUL machines.
124
Typical Starting Current per Compressor
28A
29A
23A
Utilization Range
360 - 440
342 - 402
414 - 508