TABLE 1: GENERAL DATA - CH060-120 5-10 TON HORIZONTAL MODELS
Model
Nominal Cooling(Ton)
Cooling Performance
Gross Cooling Capacity(Btuh)
Design CFM
EER
Compressor-Type
Number Used
Evaporator Coil-Type
Face Area(sq ft)
Rows/FPI
Condenser-Type
Number Used/Tons Capacity
Nominal Water flow rate (gpm)
Condenser Water Connections
Evaporator Fan-Type
Number Used
Diameter x Width (in)
Drive
Motor HP (Standard/Oversize)
Filters
Number Used-Size(in)
Condensate Drain Connection
Weight
NOTE: Cooling performance is rated at 80∞ F dry bulb 67∞ F wet bulb entering air temperature, CFM listed, 85∞ F entering
95∞ F leaving water temperature, and water flow rate listed. Gross capacity does not include the effect of evapora-
tor fan motor heat.
4
CH060
CH096
5
64100
101800
2000
13.3
1
Copper Tubes, Aluminum Fins
5.28
3/13
1/5
15
1" FPT
1-1/4" FPT
Centrifugal, Forward Curved
1
10x10
Adjustable Belt
1/NA
2-20x20x2
2-20x25x2
1-20x20x2
460
036-21217-001-B-1203
CH120
8
126000
3200
4000
13.4
12.0
Scroll
2
9.17
9.17
3/13
3/13
Coaxial
2/4
24
1-1/4" FPT
2
10x8
10x8
1.5/2
2-20x25x2
1-20x20x2
3/4FPT
710
760
Unitary Products Group
10
2
2/5
30
2
2/3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ch060Cu060aCu096aCu120aCu180aCu240a ... Show all

Table of Contents