036-33072-001 Rev. A (0601) re-setable lock-out relay will shut off the compressor in the GENERAL event of pressure switch trip during operation. Control circuit operates on 24V, and features an oversized transformer. Optional anti-short circuit timers can be field/factory installed. Our units are designed to accommodate the ever-changing installation requirements of today's market.
036-33072-001 Rev. A (0601) FIGURE 1: TYPICAL INSTALLATION LAYOUT (CU180 SHOWN) INSTALLATION WARNING PRE-INSTALLATION INSPECTION OF EQUIPMENT PRIOR TO MOUNTING UNIT, CHECK INDIVID- All units are factory tested to ensure safe operation and qual- UAL UNIT WEIGHTS AND VERIFY LIFTING ity assembly.
Common vibration and sound levels associated with commercial equipment may be objectionable to people or equipment. Install thermostats, air supplies and returns so that each unit will operate only on individual unit control. TABLE 1: GENERAL UNIT INFORMATION Model CU060 CU096 CU120 CU180 CU240 CU300...
036-33072-001 Rev. A (0601) FIGURE 4 : DIMENSIONS CU240/CU300 WATER PIPING Water piping should include shutoff/balancing valves so that All factory installed water piping terminates inside the unit. the unit can be serviced without shutting down and draining Multi-condenser units feature manifolded single water in and the entire water supply circuit.
036-33072-001 Rev. A (0601) mains water is being used, make sure the valve closes soon CONDENSOR PRESSURE CONTROL after the compressor stops. If the flow does not stop after a few minutes, raise the opening pressure by turning the Water regulating valves provide control of the quantity of con- adjusting shaft caunter clockwise until the flow stops.
036-33072-001 Rev. A (0601) DUCTWORK return is desired, duct connection flanges may be secured When installing ductwork, adhere to local Codes and sensible directly to the air intake opening of the 5 through 15 ton units practice. Minimize duct runs and avoid abrupt changes in -filters are accessible from the right hand side.
036-33072-001 Rev. A (0601) EVAPORATOR BLOWER DISCHARGE CONVERSION WARNING All models can be field converted to the alternate evaporator DISCONNECT AND LOCK OUT POWER WHEN discharge orientation. All models ship with vertical fan dis- SERVICING UNIT. FAILURE TO DO SO MAY charge as standard.
Page 13
036-33072-001 Rev. A (0601) Unit requires installer to provide a 24volt thermostat with The CU6300 -25 ton models feature three independent com- appropriate heating and cooling stages as needed. For low pressor stages. A multi-stage commercial thermostat (ie. voltage wiring, 18 gauge wire may be used for up to 50 feet Honeywell T7300 series), or other type of multi-step control- lengths.
036-33072-001 Rev. A (0601) There is no negative impact on durability caused by operating TABLE 6: REFRIGERANT CHARGES three pase Scroll compressors in the reversed direction for a Ref. Charge short period of time (under one hour). However, after several No.
036-33072-001 Rev. A (0601) MAINTENANCE/SERVICE EVAPORATOR AND CONDENSER COILS Inspect the evaporator coil at filter change intervals. Inspect the condenser coil at least semi-annually. A dirty condenser CAUTION coil will result in elevated condensing pressures and poor unit performance. Dirty or clogged evaporator coils causes low suction pressure and lost capacity.