Unit Dimensions Dj180, 210, 240 & 300; Minimum Clearances - York DJ 180 Technical Manual

Single package gas/electric units and single package air conditioners
Hide thumbs Also See for DJ 180:
Table of Contents

Advertisement

TABLE 26: MINIMUM CLEARANCES
LOCATION
Front
Rear
Left Side (Filter Access)
Right Side (Cond. Coil)
1
Below Unit
2
Above Unit
1.
Units may be installed on combustible floors made from wood or
class A, B, or C roof covering material.
2.
Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge outlet.
3. If economizer is factory installed, the unassembled rain hood
must be removed from its ride along position in front of evapora-
tor coil, or in the outdoor air compartment, prior to final installa-
tion.
POWER EXHAUST
SUPPLY AIR
RAIN HOOD
COMPARTMENT
(on Return Air Compartment)
REAR VIEW
FIGURE 6 - UNIT DIMENSIONS DJ180, 210, 240 & 300 (RAINHOOD)
32
CLEARANCE
36"
24" (Less Economizer)
49" (With Economizer)
24" (Less Economizer)
3
36" (With Economizer)
36"
0"
72" With 36" Maximum
Horizontal Overhang (For
Condenser Air Discharge)
ECONOMIZER
MOTORIZED
DAMPER
RAIN HOOD
(on Outdoor Air Compartment)
36-5/8"
5"
DETAIL "Y"
UNIT WITH RAIN HOODS
NOTE: ELEC / ELEC Models: Units and ductwork are
approved for zero clearance to combustible material
when equipped with electric heaters.
GAS / ELEC Models: A 1" clearance must be
provided between any combustible material and the
supply air ductwork for a distance of 3 feet from the
unit.
The products of combustion must not be allowed to
accumulate within a confined space and recirculate.
Locate unit so that the vent air outlet hood is at least:
• Three (3) feet above any force air inlet located
within 10 horizontal feet (excluding those integral to
the unit).
• Four (4) feet below, four horizontal feet from, or one
foot above any door or gravity air inlet into the
building.
• Four (4) feet from electric and gas meters,
regulators and relief equipment.
ECONOMIZER / MOTORIZED DAMPER
AND POWER EXHAUST RAIN HOODS
FIXED
OUTDOOR AIR
INTAKE HOOD
(located on
Return Air
Compartment)
16-1/8"
28-3/16"
261660-YTG-C-0707
1" CONDENSATE
DRAIN
(Must be trapped)
92"
LH VIEW