Sound Power Rating; Capacity Ratings - (Ari 360); Gas Heat Ratiings - York DJ 180 Technical Manual

Single package gas/electric units and single package air conditioners
Hide thumbs Also See for DJ 180:
Table of Contents

Advertisement

261660-YTG-C-0707
TABLE 1: SOUND POWER RATING
ESP
UNIT
CFM
SIZE
IWG
180
6,000
1.00
210/240
8,000
1.00
300
10,000
1.30
1.
These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee
requiring a dBA value or sound data in any other form than sound power level ratings.
2.
At a distance of 10 feet from the blower.
TABLE 2: CAPACITY RATINGS - (ARI 360)
MODEL
COOLING ONLY
DJ180C/E00
DJ210C/E00
DJ240C/E00
DJ300C/E00
COOLING WITH GAS HEAT
DJ180N/S
DJ210N/S
DJ240N/S
DJ300N/S
COOLING WITH ELECTRIC HEAT
DJ180E18
DJ180E36
DJ180E54
DJ180E72
DJ210E18
DJ210E36
DJ210E54
DJ210E72
DJ240E18
DJ240E36
DJ240E54
DJ240E72
DJ300E18
DJ300E36
DJ300E54
DJ300E72
1.
Certified in accordance with the Unitary Large Equip-
ment certification program which is based on ARI Stan-
dard 340/360.
2.
EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu's per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3.
IPLV = Integrated Part Load Value.
Unitary Products Group
1
BLOWER
RPM
BHP
63
125
1,080
4.60
99
1,120
6.65
102
102
1160
12.5
108
108
1
2
MBH
EER
IPLV
178
12.0
12.5
208
11.7
12.7
230
11.3
12.0
292
10.5
11.2
178
12.0
12.5
208
11.7
12.7
230
11.3
12.0
292
10.5
11.2
178
12.0
12.5
178
12.0
12.5
176
11.8
12.2
176
11.8
12.2
208
11.7
12.7
208
11.7
12.7
206
11.5
12.4
206
11.5
12.4
230
11.3
12.0
230
11.3
12.0
228
11.1
11.7
228
11.1
11.7
292
10.5
11.2
292
10.5
11.2
290
10.3
11.0
290
10.3
11.0
SOUND POWER (db 10
Octave Band Centerline Frequency (Hz)
250
500
1,000
99
89
82
84
92
85
87
98
91
93
TABLE 3: GAS HEAT RATIINGS
MODEL
3
DJ180N/S24
DJ180N/S32
DJ210N/S24
DJ210N/S32
DJ240N/S24
DJ240N/S32
DJ300N/S24
DJ300N/S32
NOTE: All gas units are two-stage heating.
First stage is 50% of total.
S.S.E. = Steady State Efficiency (80%) - output divided by input.
For units with VFD and electric or gas heat, the
speed of the indoor blower motor continues to
be controlled by duct static pressure via the
VAV control board.
If there are VAV boxes present in the duct sys-
tem, the boxes must be driven to the full-open
position using a customer-supplied power
source to assure adequate airflow across elec-
tric heating elements or gas heat exchanger
tubes.
-12
Watts)
SWL
dB(A)
2,000
4,000
8,000
77
72
67
89
80
75
70
92
86
81
76
98
MBH INPUT
MBH OUTPUT
300
400
300
400
300
400
300
400
dB(A)
@
2
10Ft.
56
59
65
240
320
240
320
240
320
240
320
9

Hide quick links: