TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-MH)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE
GENERAL
These devices are used indoors (ta 40 C)
in places where emergency luminaires are
needed. The luminaires GR-270 and GR-
272 are suitable for corridors lighting and
the GR-271 and GR-273 for open area
lighting. Each device must be permanently
connected to mains power supply. In
normal operation the battery is charging. In
case of a mains power supply failure the
device will light the illumination led
automatically in emergency mode. When
the mains power supply is restored the
device turns to normal operation.
INSTALLATION
To install the luminaire follow the
installation instructions οn page 2.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance
or testing must be done by authorized
personel only.
2. The device must be connected to the
mains power supply thru a fuse dependent
by the total amount of the line's power
load.
3. It is sugested to check every month the
indication LED for battery charging, and by
pushing the TEST button (use a pointy tool
Page 1 from 4
NON MAINTAINED SPOT LIGHT EMERGENCY
LUMINAIRES WITH 1 WHITE POWER LED
GR-270
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Thank you for your trust in our products
Olympia Electronics - European manufacturer
(for LED MODULE specifications see page 4)
GR-271
220-240V AC / 50-60Hz
2.4W / 2.7VA
3.6V/1.5Ah
Deep discharge and overcharge protection
Charge, TEST button
1.5 hour
1 white power LED
160lm
Up to 95%
ABS/PC, PC
Ø125 x 65 mm
3 years (1 year for the battery)
with diameter of 2mm max.) to check the
o
emergency cirquit. The illumination LED
should light as long as the TEST button is
pressed. In the opposite condition contact
the installer.
4. It is sugested to check every 6 months
the minimum autononous duration by
disconnecting the mains power supply.
Count the time that the luminaire lights and
in case of less time than the minimum
autonomous duration the battery must be
r e p l a c e d . I f t h e m e a s u r e d t i m e i s
considerably less than the minimum
autonomous duration
I n c a s e o f b a t t e r y o r l i g h t s o u r c e
replacement, these must be replaced by
parts of the same type, by the manufacturer
or by a competent person.
5. In case of inactive use for a period
greater than 2 months, disconnect the
b a t t e r y b y p u l l i n g o u t t h e b a t t e r y 's
connector.
6. I s not allowed to discard batteries in
t i
to common trash bins, they must be
discarded only
points. Do not incinerate.
GR-272
24 hours
3 hours
120lm
IP40
o
5 to 40 C
380gr.
contact the installer.
in battery recycling
923270000_09_004
GR-273

Advertisement

loading

Summary of Contents for olympia electronics GR-270

  • Page 1 The illumination LED in places where emergency luminaires are should light as long as the TEST button is needed. The luminaires GR-270 and GR- pressed. In the opposite condition contact 272 are suitable for corridors lighting and the installer.
  • Page 2 4 Refit the reflector (mind the correct orientation), tighten the screw securely and the luminaire is ready for mounting. NOTE!! After finishing the installation you must power the luminaire for, at least, 24 hours for battery charging to perform the nominal autonomy. GR-270, GR-272 Corridor lighting CHARGE...
  • Page 3 Mark these two drilled points on the required mounting location, drill the holes and install the supplied plastic plugs. ATTENTION!! Especially for the GR-270 and GR-272 luminaire installation on the ceiling you must align the base with the indications on the luminaire’s base.
  • Page 4 Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-271Gr-272Gr-273