M1M 30 POWER METER USER MANUAL
• BYTE
BYTE comprises three parts – bits per byte, parity bit and stop bit.
CONF
COMM
BYTE
The optional byte formats include:
BYTE
8E1
8O1
8N1
8N2
Modbus TCP/IP (M1M 30 Ethernet)
• DHCP
If DHCP is set as "YES", it indicates that the IP address and subnet mask assigned by the host will be
used.
CONF
COMM
DHCP
The default state of DHCP is "NO", i.e. turned off.
• IP
IP comprises 4 segments. Each time Button "Enter" is pressed, the next segment can be set.
CONF
COMM
IP
The default IP address is: 192.168.2.252.
The device and the host must share the same network, or their communication is not possible.
Description
8 even parity bits and 1 stop bit
8 odd parity bits and 1 stop bit
8 No Parity bits and 1 stop bit
8 No Parity bits and 2 stop bits
43