7.3.Historicals (HIST)

In this section it is possible to carry out configurations related to Historicals functionalities. Historicals
functionalities allow to store measurement variable (VARB) at a set Time (TIME).
Historicals functionalities can be set for one of following group of parameters:
Group
REAL
ENRG
PWQT
Time interval (TIME)
TIME parameter represents the time interval for storing measurement inside the flash memory.
The default of this parameter is 15 minutes, and the adjustable range is 1-60 minutes.
Variables
Phase voltage, line voltage, current, neutral current, active power, reactive power,
apparent power, total active power, total reactive power, total apparent power,
frequency
Active energy consumption, active power generation, reactive energy consumption,
reactive generation of electrical energy, apparent energy
Power factors (per phase and total) THD voltage, THD current, unbalances voltage
(phase voltage and line voltage), unbalances current
CONF