Carrier Comfort Network Interface - Carrier AquaEdge 19DV Series Installation Instructions Manual

Table of Contents

Advertisement

CARRIER COMFORT NETWORK INTERFACE

The Carrier Comfort Network
wiring is supplied and installed by the electrical contractor. It
consists of shielded, 3-conductor cable with drain wire.
The system elements are connected to the communication bus
in a daisy chain arrangement. The positive pin of each system
element communication connector must be wired to the posi-
tive pins of the system element on either side of it. The nega-
tive pins must be wired to the negative pins. The signal ground
pins must be wired to the signal ground pins. See Fig. 16 for lo-
cation of the CCN network connections on the terminal strip
labeled CCN.
NOTE: Conductors and drain wire must be 20 AWG (Ameri-
can Wire Gage) minimum stranded, tinned copper. Individual
conductors must be insulated with PVC, PVC/nylon, vinyl,
Teflon
1
, or polyethylene. An aluminum/polyester 100% foil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,
or Teflon with a minimum operating temperature range of –4°F
to 140°F (–20°C to 60°C) is required. See table below for ca-
bles that meet the requirements.
MANUFACTURER
ALPHA
AMERICAN
BELDEN
COLUMBIA
When connecting the CCN communication bus to a system ele-
ment, a color code system for the entire network is recom-
mended to simplify installation and checkout. The following
color code is recommended:
CCN BUS
CONDUCTOR
SIGNAL TYPE
INSULATION
+
GROUND
If a cable with a different color scheme is selected, a similar
color code should be adopted for the entire network.
At each system element, the shields of its communication bus
cables must be tied together. If the communication bus is en-
tirely within one building, the resulting continuous shield must
be connected to ground at only one single point. See Fig. 16. If
the communication bus cable exits from one building and en-
ters another, the shields must be connected to ground at the
lightning suppressor in each building where the cable enters or
exits the building (one point only).
To connect the 19DV chiller to the network, proceed as follows
(see Fig. 16):
1.
Route wire through knockout in back of control panel.
2.
Strip back leads.
3.
Crimp one no. 8 size spring spade terminal on each
conductor.
4.
Attach red to "+" terminal and white to "G" terminal and
black to "–" terminal of CCN Network interface located in
the control panel.
1. Teflon is a registered trademark of DuPont.
(CCN) communication bus
®
CABLE NO.
2413 or 5463
A22503
8772
02525
CCN NETWORK
INTERFACE
(CONTROL PANEL)
COLOR
Red
+
White
G
Black
Step 6 — Install Field Insulation
Protect insulation from weld heat damage and weld
splatter. Cover with wet canvas cover during water pip-
ing installation.
When installing insulation at the jobsite, insulate the following
components:
compressor motor
economizer
evaporator shell
evaporator tube sheets
suction piping
motor cooling drain
inhibitor reclaim piping
purge tank and connecting tubing
low side of purge system independent refrigerant circuit
refrigerant liquid line to evaporator
NOTE: Insulation of the waterbox covers is applied only at the
jobsite by the contractor. When insulating the covers, make
sure there is access for removal of waterbox covers for servic-
ing. See Fig. 26.
33
CAUTION

Advertisement

Table of Contents
loading

Table of Contents