Ground Connector - Carrier AquaEdge 19DV Series Installation Instructions Manual

Table of Contents

Advertisement

LEGEND
1 — Disconnect
2 — Chilled Water Pump Starter
3 — Condenser Water Pump Starter
4 — Cooling Tower Fan Starter
(Low Fan, High Fan)
5 — Vents
6 — HMI (hidden)
7 — Unit-Mounted VFD
8 — Control Panel
9 — Strainers
10 — Chilled Water Pump
11 — Condenser Water Pump
12 — Pressure Gages
Piping
Control Wiring
Power Wiring
VFD MAX INPUT AMPS
CARRIER 32VSS0850
1
1
1
2
5
12
9
10
11
NOTES:
1. Wiring and piping shown are for general point-of-connection only and are not
intended to show details for a specific installation. Certified field wiring and
dimensional diagrams are available on request.
2. All wiring must comply with applicable codes.
3. Wiring not shown for optional devices such as:
• Remote Start/Stop
• Remote Alarms
• Optional Safety Device
• 4 to 20 mA Resets
• Optional Remote Sensors
4. IMPORTANT: Carrier suggests that a structural engineer be consulted if trans-
mission of vibrations from mechanical equipment is of concern.
5. Isolation valves are recommended on the evaporator and condenser water pip-
ing to each chiller for service.
6. Operating environment — Chiller should be installed in an indoor environment
where the ambient temperature is 40 to 104°F (4 to 40°C) with a relative
humidity (non-condensing) of 95% or less. To ensure that electrical compo-
nents operate properly, do not locate the chiller in an area exposed to dust, dirt,
corrosive fumes, or excessive heat and humidity.
7. Be sure to pipe
Fig. 25 — 19DV Chiller with VFD
Table 14 — VFD Conductor Usage
STANDARD 100 KAIC LUG CAPACITY (PER PHASE)
NO. OF CONDUCTORS
4
1
6
3
/
-in. VFD condensate pipe to drain.
8
CONDUCTOR RANGE
4/0 - 500 kcmil
32
7
8

GROUND CONNECTOR

2/0