Siemens SIMATIC S7-1500 Function Manual page 179

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
The URLs are structured as follows:
● Protocol identifier "opc.tcp://"
● IP address
– 192.168.178.151
– 192.168.1.1
● TCP Port number
– Default: 4840 (standard port)
Dynamic IP addresses
In the example below, the IP address for the PROFINET interface [X2] has not yet been
specified.
Figure 9-15
The placeholder "<dynamically>" appears in the table.
The IP address of this PROFINET interface is set later on the device, e.g. via the display of
the CPU.
178
The IP address at which the OPC UA server can be accessed from the Ethernet
subnet 192.168.178.
The IP address at which the OPC UA server can be accessed from the Ethernet
subnet 192.168.1.
The port number can be changed under "OPC > UA > Server > Port".
Display of the server addresses with dynamic IP address
Function Manual, 11/2019, A5E03735815-AH