Siemens SIMATIC S7-1500 Function Manual page 100

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

4. Set the parameters for secure communication in the "Start value" column.
– "ActivateSecureConn": Activation of secure communication for this connection. If this
– "TLSServerCertRef": Enter the value 2 (reference to the CA certificate of the
– "TLSClientCertRef": ID of the own X.509-V3 certificate.
5. Create one of the instructions TSEND_C, TRCV_C or TCON in the program editor.
6. Interconnect the CONNECT parameter of one of the instructions TSEND_C, TRCV_C or
TCON with the tags of the data type TCON_IP_V4_SEC.
Settings at the TLS server
To set up a secure TCP connection in the TLS server, follow these steps:
1. Create a global data block in the project tree.
2. Define a tag of the data type TCON_IP_4_SEC in the global data block.
The example below shows the global data block "Data_block_1" in which the tag "SEC
connection 1 TLS-Server" of the data type TCON_IP_V4_SEC is defined.
Figure 6-20
IP_V4_SEC_Server
3. Set the connection parameters of the TCP connection in the "Start value" column. For
example, enter the IPv4 address of the TLS client for "RemoteAddress".
Communication
Function Manual, 11/2019, A5E03735815-AH
parameter has the value FALSE, the subsequent security parameters are irrelevant.
You can set up a non-secure TCP or UDP connection in this case.
TIA Portal project (SHA256) or the value 1 (reference to the CA certificate of the TIA
Portal project (SHA1)). If you use a different CA certificate, enter the corresponding ID
from the certificate manager of the global security settings.
Open User Communication
6.11 Secure Open User Communication
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents