System Features

Feature
Quick connection to compatible LYNXR-I series control panels
Simple programming using a 7720P programming tool
Reports fire, burglary, and status messages via wireless network
Reports fire, burglary, and status messages via internet
Allows uploading and downloading of control panel data via the wireless
network.
Allows uploading and downloading of control panel data via internet.
Provides 2-way communication with the control using ECP messaging
Sends reports in Contact ID format
Supports two hardwire zone trigger inputs (zones 6 and 7)
Easy CAT-5 10 BaseT connection to a hub or router
Installs behind firewalls without compromising network security
Supports dynamic or static IP addressing
Supports remote control of alarm system via Remote Services Feature
* As a backup to the internet.
The LYNXDM-GSM and LYNXDM-IGSM provide the following types of supervision and module fault detection:
Network communication failure: In the event the AlarmNet network does not hear a supervisory message
from the module within a specified time ("Supervision" option, 24 hours, 30 days, or none), AlarmNet
notifies the central station of a communication failure.
Communication path failure: In the event the module detects a communication path failure, the control
panel can be notified of a trouble condition with the module after a specified time has elapsed.
Remote Services Features
The Remote Services Features can only be used with LYNXR-I Series controls Revision 16 or later. Multi
Mode (E-mail notification) is intended as a convenience for the user, and does not replace Central Station
reporting of critical events (alarms, troubles, etc.).
Remote Services allow the end user to communicate with their Security System remotely via several features.
Availability of this service is controlled by the dealer via the web-based programming tool on the AlarmNet
Direct website. Once enabled, the specific programming fields associated with these features can be
programmed either remotely using the AlarmNet Direct website or locally using the 7720P Programming Tool.
These new web services will allow users to:
• Receive e-mail and text message notification of system events (Multi-Mode feature)
• Access their security system from a computer via a website (Remote Access feature)
• Perform system functions and receive confirmations using text messages (SMS feature)

INSTALLATION

The incoming wiring can be routed through the opening in the rear of the back plate or through the wire
troughs in the mount's case back. A wire knockout is also provided in the desk mount front case.
Installing the desk mount
1. Route the incoming power, telephone and/or internet wiring through the appropriate openings in the
mount's rear case.
2. Route incoming power, telephone and communications, etc. wiring through the mount's front case.
3. Proceed to Wiring the LYNXR-I or LYNXR-ISIA section.
Installing the wall mount
1. Locate the rear case over the mounting surface such that the opening in the case is aligned with the
wire/cable access opening (in the mounting surface).
If the wiring will be run externally, it should be routed through the wire troughs in the wall mount case back.
- 2 -
LYNXDM-GSM
LYNXDM-IGSM
x
x
x
x
x
x*
x
X
x*
X
x
x
x
x
x
x
x
x
x
x
x