Firepower Clearline AKW Installation Instructions And Maintenance Manual page 24

Twin-wall chimney
Table of Contents

Advertisement

These are the recommended heights that you can use as a way of
meeting the building regulation requirements.
Very simplified these recommendations can be summed up in the
following way:
The horizontal distance from the top of the flue pipe to the roof
should be at least 2300mm, or above the ridge. Unless the flue
termination is within 600mm horizontally of the ridge, in which case
the flue should be at least 600mm above the ridge.
Flue outlet height unsafe areas diagram
The grey area in the picture shows where the flue must not
terminate on a roof with standard (non flammable) roof material.
For further information refer to building regs:
https://www.gov.uk/government/uploads/system/uploads/attachme
nt_data/file/468872/ADJ_LOCKED.pdf