Firepower Clearline AKW Installation Instructions And Maintenance Manual page 10

Twin-wall chimney
Table of Contents

Advertisement

500-880MM ADJUSTABLE LENGTH
Adjustable lengths come with two locking bands – distance to combustibles
remains at 50mm, the same as all standard lengths.
Each adjustable length comes with an extra short length of rockwool which gets
compressed to ensure insulation continues throughout. Care must be taken to
ensure that when assembled to required length no air gaps are left.
There is a high-temp plastic seal in the adjustable length locking band to avoid
any movement once length has been adjusted to required height. The locking
band fits onto the lower lip of the pipe.
350-500MM ADJUSTABLE LENGTH
250-350MM ADJUSTABLE LENGTH
500MM TESTING LENGTH
Working length 457mm, including analysis port
PELLET GASKET
A rubber seal used on condensing installations to stop the condensates from
penetrating the flue. The Product Designation for Clearline AKW with seals fitted
for condensing appliances is:
EN1856-2 T200-P1-W-V2-L50040 0(20)
Code:02-***-014
Code:02-***-015
Code:02-***-016
Code:02-***-019
Code:15-***-102