4.15

Servomotors

Warnings
To avoid accidents, material or environmental
damage, observe the following instructions!
Avoid opening, modifying or forcing the actuators.
WARNING
 All interventions (assembly and installation operations,
assistance, etc.) must be carried out by qualified personnel.
 Before modifying the wiring in the connection area of the
servomotor, fully disconnect the burner control device from
the power supply (omnipolar separation).
 To avoid the risk of electrocution, protect the connection ter-
minals in a suitable manner and correctly fix the cover.
 Check the wiring is in order.
 Falls and collisions can negatively affect the safety func-
tions. In this case, the unit must not be operated, even if it
displays no evident damage.
Assembly notes
 Check the relevant national safety standards are respected.
 The connection between the actuator command shaft and
the control element must be rigid, without any mechanical
play.
 To avoid an excessive load on the bearings due to rigid
hubs, the use of compensation clutches without any
mechanical play is recommended (e.g. metal bellows-type
clutches).
Installation notes
 Arrange the HV ignition cables separately, as far as possible
from the control box and the other cables.
 To prevent the risk of electrocution, check that the 230 V AC
section of the servomotor is completely separated from the
low voltage section.
 The static torque is reduced when the electrical supply of the
actuator is switched off.
 The housing cover may only be removed for short periods of
time for wiring or when making the addressing. In similar
cases, make sure that dust or dirt does not penetrate inside
the actuator.
 The top side of the board carries a cover which affords pro-
tection against direct contact. This protective cover must not
be removed! The underside side of the board must not be
touched.
During the maintenance or replacement of the
actuators, be careful not to invert the connec-
tors.
WARNING
Technical description of the burner
17
GB
S8837
Technical data
Model
Operating voltage
230V - 50Hz via the connection cable to
Safety class
Extra low-voltage with safe isolation
Power absorption
Protection level
Cable connection
Rotation direction
Nominal torque (max)
Holding torque (max)
Running time (min.) for
90°
Weight
Environmental conditions:
Operation
Temp. range
Humidity
662R2111
662R2127
the base unit
from mains voltage
6.45 VA
3 VA
EN 60 529, IP 54
with suitable cable grommets
with terminals
- Anticlockwise (standard)
- Clockwise (inverted rotation)
20 Nm
6 Nm
20 Nm
6 Nm
60 s.
approx. 1.7 kg
DIN EN 60 721-3-3
-20...+60°C
< 95% rh
Fig. 11
Tab. G
20123768