Attachment - Using Devices At Altitudes Greater Than 2000 M Above Sea Level - Eaton ESR5-NE-51-24VAC-DC Manual

Safety relay
Table of Contents

Advertisement

14 Attachment - using devices at altitudes greater than 2000 m above sea level
14 Attachment - using devices at altitudes greater than 2000 m above sea level
The following section describes the special conditions for using
ESR5-NE-51-24VAC-DC devices at altitudes greater than
2000 m above sea level.
Observe the relevant device-specific data (technical data,
derating, etc.) according to the product documentation for the
individual device.
Using the device at altitudes greater than 2000 m above sea level up to
max. 4500 m above sea level is possible under the following conditions:
▶1. Limit the nominal input voltage (U
Observe the technical data for the device.
U
according to the technical data for the
N
device
< 150 V AC/DC
> 150 V AC/DC
▶2. Limit the maximum switching voltage in accordance with the table
below. Observe the technical data for the device.
Max. switching voltage according to the
technical data for the device
< 150 V AC/DC
> 150 V AC/DC
▶3. Reduce the maximum ambient temperature for operation by the
corresponding factor in accordance with the table below.
▶4. If derating is specified, offset all the points of the derating curve by the
corresponding factor in accordance with the table below.
Altitude above
Temperature
sea level
derating factor
2000 m
1
2500 m
0.953
3000 m
0.906
3500 m
0.859
4000 m
0.813
4500 m
0.766
ESR5-NE-51-24VAC-DC 12/19 MN049002EN www.eaton.com
) in accordance with the table below.
N
U
when used at altitudes greater than
N
2000 m above sea level
U
according to the technical data for the device still valid
N
Limited to max. 150 V AC/DC
Max. switching voltage when used at altitudes greater
than 2000 m above sea level
U
according to the technical data for the device still valid
N
Limited to max. 150 V AC/DC