Rear Vent - Horizontal Termination
No Elbow
Note: Use DVP Series
components only.
Figure 4.22
One 45° Elbow
Note: Use DVP Series
components only.
WARNING! Risk of Fire! This vent configuration is not allowed with
NDV42-IFT/NDV42L-IFT
Note: To achieve optimum flame appearance, the
vent configurations shown in Figure 4.13 and Figure
4.24 are recommended.
Figure 4.23
Heatilator • NDV30-IFT, NDV33-IFT, NDV36-IFT, NDV36-IFT-NVR, NDV42-IFT Installation Manual • 2620-980 Rev. C • 8/20
H
1
H
Maximum
1
NDV30-IFT
NDV33-IFT
18 in.
NDV36-IFT
NDV36-IFT-NVR
NDV42-IFT
12 in.
H
Maximum
1
NDV30-IFT
NDV33-IFT
9 in.
NDV36-IFT
NDV36-IFT-NVR
NDV42-IFT
NOT ALLOWED
H
1
457 mm
305 mm
229 mm
29