Oil Return Management Function (Single Compressor); Oil Return Management In Hybrid Manifolding; High And Low Pressure Protection - Danfoss VZH088-G single Application Manuallines

Inverter scroll compressors, r410a
Table of Contents

Advertisement

Application Guidelines
Oil return management
function (single
compressor)
Oil return management
in hybrid manifolding
High and low pressure
protection
High pressure
Operating conditions
The discharge gas temperature must not exceed
135°C.
A discharge gas temperature protection device
must be installed on all heat pumps. In reversible
air-to-air and air-to-water heat pumps the
discharge temperature must be monitored
during development test by the equipment
manufacturer.
The compressor must not be allowed to cycle
on the discharge gas thermostat. Continuous
operations beyond the compressor's operating
range will cause serious damage to the
compressor!
A DGT accessory is available from Danfoss: refer
to accessories pages at the end of this document.
Insufficient oil level can be the result of oil
depositing itself in pipes and heat exchangers.
The oil deposit can be returned to the crankcase,
by increasing velocity for short periods, at
regular time intervals or when velocity is too low
to ensure adequate oil returns.
With oil return management these two oil return
mechanisms can be programmed in the CDS303.
With oil return management function enabled,
the CDS303 performs oil return by boosting the
compressor speed to 4200 rpm (70 rps) for a
selectable duration as programmed in parameter
28.13. The boosts are performed at fixed time
intervals (as programmed in parameter 28.12) or
if the compressor speed has been less than 3000
Use the accessory "oil level switch" with the
appropriate compressor housing having the
According to EN378-2, a high-pressure (HP) safety
switch is required to shut down the compressor.
The high-pressure switch can be set to lower
values depending on the application and
ambient conditions. The HP switch must either be
placed in a lockout circuit or consist of a manual
reset device to prevent cycling around the high-
The discharge gas thermostat accessory kit (code
no.7750009) includes all components required
for installation, as shown below. The thermostat
must be attached to the discharge line within
150 mm from the compressor discharge port and
must be thermally insulated and tightly fixed on
the pipe.
Thermostat
Discharge line
Bracket
rpm (50 rps) for too long (as programmed in
28.11) whichever occurs first. Thus the maximum
time between two consecutive oil return boosts
is programmed in 28.12.
Factory
ID
Name
Setup
Oil Return
2810
On
Management
2811 Low Speed
60
Running Time
2812 Fixed Boost
24
Interval
2813 Boost Duration
30
Considering oil return risk, split system
with more than 10m piping length need
mandatory application approval by Danfoss
application specialists.
fitting preassembled and refer to the VZH hybrid
manifold guideline (FRCC.PC.049).
pressure limit. If a discharge valve is used, the HP
switch must be connected to the service valve
gauge port, which must not be isolated. The HP
switch must be connected to the CDS303 input
37 or an external contactor placed between the
drive and the compressor.
Insulation
"long pipe
Unit
(25-30m)"
On
30
min
6
h
60
s
43
FRCC.PC.023.A8.02

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VZH088-G single and is the answer not in the manual?

This manual is also suitable for:

Vzh088-h singleVzh088-g manifoldedVzh088-h manifoldedVzh088-j singleVzh088-j manifoldedVzh117-g single ... Show all

Table of Contents