Technical Data - Eaton ESR5-BWS-31-24VAC-DC Manual

Safety relay
Table of Contents

Advertisement

8 Technical data

Input data
Nominal input voltage U
N
Input voltage range (factor)
Typical input current
Voltage at input/start and feedback circuit
Typical response time
Typical release time
Recovery time
Operating voltage display
Status display
Protective circuit
Output data
Contact type
Contact material
Minimum switching voltage
Maximum switching voltage
Limiting continuous current
Maximum inrush current
Inrush current, minimum
Sq. Total current
2
2
2
2
(I
)
= (I
)
+ (I
)
+ (I
)
TH
1
2
3
Interrupting rating (ohmic load) max.
Maximum interrupting rating (inductive load)
Switching capacity min.
Mechanical service life
Switching capacity (360 cycles/h)
Switching capacity (3600 cycles/h)
Output fuse
ESR5-BWS-31-24VAC-DC 12/19 MN049005EN www.eaton.com
24 V AC/DC
0.85 - 1,1
150 mA AC
70 mA DC
24 V DC
25 ms (manual start)
100 ms (automatic start)
10 ms (single-channel)
1 s
Green LED
Green LED
Fuse PTC resistor
3 enabling current paths
1 signaling current path
AgSnO
+ 0,2 μm Au
2
15 V AC/DC
250 V AC/DC
6 A
6 A
25 mA
2
72 A
(see derating curve → Figure 3, page 9)
144 W (24 V DC, τ = 0 ms)
288 W (48 V DC, τ = 0 ms)
77 W (110 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms)
48 W (24 V DC, τ = 40 ms)
40 W (48 V DC, τ = 40 ms)
35 W (110 V DC, τ = 40 ms)
33 W (220 V DC, τ = 40 ms)
0.4 W
7
10
cycles
6 A (24 V DC)
5 A (230 V AC)
3 A (24 V (DC-13))
3 A (230 V (AC-15))
10 A gL/gG NEOZED (N/O contact)
8 Technical data
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

180413Esr5-no-31-24vac-dc118702

Table of Contents