Digital Inputs - ABB MotiFlex e100 OPT-MF-005 User Manual

Digital i/o

Advertisement

3.1.2 Digital inputs

Six independent digital inputs.
Input voltage range: 12-30 V DC (input current not to exceed 50 mA).
Sampling frequency: 8 kHz.
Each digital input is buffered by a TLP280 opto-isolator, allowing the input signal to be
connected with either polarity.
OPT-MF-005 Digital I/O
DIN32/64+
19
DIN32/64-
7
When the MotiFlex e100 is connected to Mint WorkBench, the digital inputs can be
configured using the Digital I/O tool. Alternatively, Mint keywords including RESETINPUT,
ERRORINPUT and STOPINPUT can be used in the command window. The state of these
specially configured digital inputs can then be viewed using the Mint WorkBench Spy
window's Axis tab. The state of all digital inputs can also be viewed using the Spy window's
I/O tab. See the Mint help file for details.
NextMove e100 / controller
Mint
OUTX(0)
Figure 3-4: Digital input - typical connection from an ABB NextMove e100
MN1950WEN
3k3
100R
Figure 3-3: DIN32/64 digital input circuit
UDN2982
9
1
10
Vcc
TLP280
DGND
User
supply
USR V+
24 V
DOUT0
DIN32/64+
DIN32/64-
USR GND
User
supply
GND
Mint
INX(32) INX(64)
/
74LVC14
OPT-MF-005 Digital I/O
3k3
19
100R
7
TLP280
Input / Output 3-3