Module Name
Temperature & Status
Emissivity
Non Greyness
Peak Picker Mode
Peak Picker Threshold
Peak Picker On Delay
Peak Picker Off Delay
Peak Picker Decay Rate
Averager Response Time 1 word O/P
Alarm Type
Alarm Temperature
Page 16
Size
Description
2 words I/P Word 1 - Temperature:
16 bit unsigned value of temperature in units as
per IRT type
Word 2 - Status:
Bit 0-2:
Not used
Bit 3:
1=Command IP active / 0=Not active
Bit 4:
1=Under range / 0=OK
Bit 5:
1=Under range / 0=OK
Bit 6:
1=Unclamped ratio IRT obscured / 0=OK
Bit 7:
1=Clipping in averager / 0=OK
Bit 8:
1=Clamped IRT sensor fail / 0=OK
Bit 9:
1=Alarm active / 0=Not active
Bit 10-11:
Not used
Bit 12-15:
Number of cyclic parameters currently outside
limits
1 word O/P
See Table 3
1 word O/P
See Table 3
1 word O/P
See Table 3
1 word O/P
See Table 3
1 word O/P
See Table 3
1 word O/P
See Table 3
1 word O/P
See Table 3
See Table 3
1 word O/P
See Table 3
1 word O/P
See Table 3