CHAPTER 11 - START-UP PROCEDURES

11.3.5 Measure Input - Natural Gas Only

1. Ensure the boiler is firing at maximum firing rate. To
manually place the boiler into high fire, reference
Section 11.3.4 on page 73.
2. Operate the unit for approximately 10 minutes.
3. Turn off all gas appliances within the building, ex-
cept the EXALT.
4. At the gas meter, record the time required to use
one cubic foot of gas.
5. Calculate Natural gas input using the following
equation:
3600 x 1000 / number of seconds recorded for one
cubic foot of gas = BTU/H.
6. The BTU/H calculated should approximate the in-
put rating listed on the unit.

11.3.6 Test High Temperature Limit

The high temperature limit can be temporarily lowered
from 210ºF [99ºC] to 102º F [39ºC] for testing.
1. Touch simultaneously on the
for 3 seconds to access the functions for the install-
er. Reference Fig. 34 on page 51.
2. Enter the installer access code "054", using the
and
soft keys to select a digit and the
soft keys to change the digit. Touch the
to enter the access code.
3. Touch the
soft key while CH & DHW Settings
icon
is highlighted.
Natural Gas 110, 155
CO2 Range
CO2 Target
O2 Range
O2 Target
CO Max
CO2 Range
Target values are equivalent to High Fire values, ensure
CO2 values measured are less than or equal to High Fire
O2 Range
Target values are equivalent to High Fire values, ensure
O2 values measured are higher than or equal to High
CO Max
74
and
soft keys
and
soft key
Table 6 - Acceptable Combustion Levels
Natural Gas 199
9.0 to 10.5%
8.5 to 10.5%
9.50%
4.85 to 2.15 %
5.75 to 2.15 %
3.95%
<150 ppm @ 9.5% CO2
9.0 to 10.0 %
8.5 to 10.0 %
CO2 measurements
4.85 to 3.0 %
5.75 to 3.0 %
Fire O2 measurements
10 ppm
4. Touch the
soft key to highlight the Boiler Set-
tings icon
then touch the
5. Touch the
soft key to highlight Lockout Tem-
perature then touch the
6. Touch the
soft key to highlight 102ºF [39ºC] then
touch the
soft key.
7. Touch the
soft key to highlight the Home Screen
icon
then touch the
8. Initiate a CH or DHW call and confirm that a High
Boiler Temperature lockout occurs once the supply
temperature reaches 102ºF [39ºC].
9. Touch any ARROW soft key to return to the Home Screen.
10. Touch simultaneously on the
3 seconds to access the functions for the installer.
11. Touch the
soft key while the CH & DHW Settings
icon
is highlighted.
12. Touch the
soft key to highlight the Boiler Set-
tings icon
then touch the
13. Touch the
soft key to highlight Lockout Tem-
perature, then touch the
14. Touch the
soft key to highlight 210ºF [99ºC] then
touch the
soft key.
15. Touch the
soft key to highlight the Home Screen
icon
then touch the
16. Touch the
soft key to reset the lockout and
return the unit to service.
Propane (All Models)
10.4 to 11.0%
<200 ppm @ 10.8% CO2
10.4 to 11.0 %
Target values are equivalent to High Fire values, ensure
CO2 values measured are less than or equal to High Fire
CO2 measurements
Target values are equivalent to High Fire values, ensure
O2 values measured are higher than or equal to High
Fire O2 measurements
soft key.
soft key.
soft key.
and
soft keys for
soft key.
soft key.
soft key.
10.80%
5.1 to 4.2 %
4.50%
5.1 to 4.2 %
10 ppm